PHOENIX CONTACT C-SAT-BOX C-SAT-BOX 2880561 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

C-SAT-BOX 2880561 PHOENIX CONTACT Surge protection device

C-SAT-BOX

2880561

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection for antenna splitters in satellite installations. IN and OUT via F connectors, 5 channels for signals from satellite installations and terrestrial antennas, grounding on the outside of the housing.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2880561
Packing unit1 pc
Catalog pagePage 180 (C-4-2017)
GTIN4046356048941
Weight per Piece (excluding packing)228.240 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height31.5 mm
Width144.9 mm
Depth71.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP40

General

Housing materialZinc die-cast
Colorsilver
Standards for cearances and creepage distancesIEC 60664-1
DIN VDE 0110-1
Overvoltage categoryII
Degree of pollution2
Mounting typeScrew mounting
TypeHousing for surface mounting
Number of positions5
Direction of actionLine-Shield/Earth Ground

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
Nominal voltage UN14 V DC (vertical)
18 V DC (horizontal)
Maximum continuous voltage UC20 V DC
Rated current400 mA
Operating effective current ICat UC≤ 2 µA (per channel)
Residual current IPE≤ 2 µA (per channel)
Nominal discharge current In(8/20) µs (line-shield)2.5 kA
Total discharge current Itotal(8/20) µs10 kA
Max. discharge current Imax(8/20) µs maximum (line-shield)2.5 kA
Nominal pulse current Ian (10/1000) µs (Core-Shield)100 A
Nominal pulse current Ian (10/700) µs (Core-Shield)100 A
Output voltage limitation at 1 kV/µs (line-shield) static≤ 80 V
Voltage protection level Up(line-shield)≤ 500 V (C2 - 4 kV / 2 kA)
≤ 120 V (C3 - 100 A)
Response time tA (line-shield)≤ 1 ns
Input attenuation aE, asym.≤ 1 dB (5 MHz ... 2,2 GHz / 75 Ω)
≤ 3 dB (5 MHz ... 2,4 GHz / 75 Ω)
Near-end crosstalk attenuation≥ 40 dB (5 MHz ... 2,4 GHz / 75 Ω)
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ohm system> 2.5 GHz
Frequency range47 MHz ... 2.5 GHz
Inductivity in seriestyp. 5 µH (f = 10 kHz)
Resistance in series3.3 Ω ±20 %
Surge protection fault messagenone
Impulse durability (line-shield)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 4 kV/2 kA
C3 - 100 A
D1 - 500 A
Impulse durability (shield-earth)C2 - 10 kA
D1 - 5 kA

Connection data

Connection methodF connector
Connection method INF connector, female
Connection method OUTF connector, female

Connection, equipotential bonding

Connection methodScrew connection

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008 + A2:2012
EN 61643-21 2013
EN 50083-2 CLASS-A

Classifications


ETIM for 2880561 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 14 V

Product Datasheet