PHOENIX CONTACT SOL-SC-2ST-0-DC-12MPPT-1300EQS SOL-SC-2ST-0-DC-12MPPT-1300EQS 1460946 PHOENIX CONTACT String box for photovoltaic installations up to 1000 .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SOL-SC-2ST-0-DC-12MPPT-1300EQS 1460946 PHOENIX CONTACT String box for photovoltaic installations up to 1000 ..

SOL-SC-2ST-0-DC-12MPPT-1300EQS

1460946

PHOENIX CONTACT

1 Pcs.

String box for photovoltaic installations up to 1000 V DC for the connection of 12x 2 strings. Same number of input and output strings. With surge protection (type 1/2), DC fire load disconnector with remote access and cable glands for the inlet and outlet side. String combiner box for photovoltaic systems up to 1,000 V DC for connecting 12x 2 strings. Same number of input and output strings. With surge protection (type 1/2), DC fire department switch disconnector with remote access, and cable glands for the input and output side.

Automation > Photovoltaic DC Stringbox
Industry Solutions (IS)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeString combiner box (SCB)
DesignDC fire department switch
Insulation characteristics
Protection classI

Electrical properties
General
MPP voltage UNmax. 1000 V DC
Non-load voltage UOCmax. 1100 V DC
Current per string Imaxmax. 20 A
Total current MPP trackermax. 40 A
Fire department switch
Rated operating current DC-21B40 A
Rated operating current DC-PV140 A
Power supply230 V AC
Signal level Remote indication contact24 V DC (floating)
Surge protection
EN typeT1
IEC test classificationT1
Protection level Up≤ 3.6 kV
Total discharge current Itotal(10/350) µs5 kA
Total discharge current Itotal(8/20) µs40 kA
Short-circuit current rating ISCPV40 A

Input data
DC
Number of inputs: Strings2 (per MPP tracker)
Number of supported MPP trackers12

Output data
DC
Number of outputs: MPP tracker2
Number of outputs: ±2 (per MPP tracker)

Connection data
DC input
Type of cable entryCable gland
Connection methodPush-in connection
Cable cross section4 mm² ... 6 mm²
External cable diameter5 mm ... 7 mm
Protective bonding and protective grounding conductor
Type of cable entryCable gland
Connection methodScrew connection
Cable cross section2x 16 mm²
External cable diameter2x 6 mm ... 12 mm
Fire department switch (emergency switching off)
Type of cable entryCable gland
Connection methodPush-in connection
Cable cross section3x 0.14 mm² ... 2.5 mm² (230 V AC)
External cable diameter6 mm ... 12 mm
Fire department switch (remote indication contact)
Type of cable entryCable gland
Connection methodPush-in connection
Cable cross section2x 0.14 mm² ... 2.5 mm²
External cable diameter6 mm ... 12 mm
DC output
Type of cable entryCable gland
Connection methodPush-in connection
Cable cross section4 mm² ... 6 mm²
External cable diameter5 mm ... 7 mm

Dimensions
Housing
Width800 mm
Height600 mm
Depth300 mm

Material specifications
Material HousingPolyester fiberglass reinforced
Material Cover/doorPolyester fiberglass reinforced

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP65
Ambient temperature (operation)-20 °C ... 50 °C

Standards and regulations
Standard designationLow-voltage switchgear and controlgear assemblies - Part 2: Power switchgear and controlgear assemblies
Standards/specificationsEN 61439-2

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.