PHOENIX CONTACT PSR-SPP-24UC/URM4/5X1/2X2/B PSR-SPP- 24UC/URM4/5X1/2X2/B 2981046 PHOENIX CONTACT Extension module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-SPP- 24UC/URM4/5X1/2X2/B 2981046 PHOENIX CONTACT Extension module

PSR-SPP-24UC/URM4/5X1/2X2/B

2981046

PHOENIX CONTACT

1 Pcs.

Extension module Single- or dual-channel contact extension, 5 NO contacts, 1 NC contact, 1 feedback circuit, width: 22.5 mm, plug-in push-in terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2981046
Packing unit1 pc
Catalog pagePage 263 (C-6-2017)
GTIN4017918915520
Weight per Piece (excluding packing)20.400 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width22.5 mm
Height112 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitudemax. 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US24 V AC/DC -15 % / +10 %
Rated control supply current IStyp. 81 mA AC
typ. 71 mA DC
Power consumption at UStyp. 1.94 W (AC)
typ. 1.7 W (DC)
Inrush current175 mA (Δt = 5 ms at Us)
Typ. starting time with Us< 20 ms (when controlled via A1)
Typical release time< 20 ms (when controlled via A1)
Recovery time< 1 s
Operating voltage display1 x green LED
Protective circuitSurge protection Varistor
Maximum switching frequency1 Hz
Filter time2 ms (at A1 in the event of voltage dips at Us)

Output data

Contact type5 enabling current paths
1 confirmation current path
1 signaling current path
Contact materialAgSnO2
Maximum switching voltage250 V AC/DC (Observe the load curve)
Minimum switching voltage5 V AC/DC
Limiting continuous current6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current20 A (Δt  100 ms)
Inrush current, minimum10 mA
Sq. Total current72 A2(observe derating)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
110 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)42 W (24 V DC, τ = 40 ms)
42 W (48 V DC, τ = 40 ms)
42 W (110 V DC, τ = 40 ms)
42 W (220 V DC, τ = 40 ms)
Switching capacity min.50 mW
Mechanical service life10x 106cycles
Switching capacity (360/h cycles)4 A (24 V DC)
4 A (230 V AC)
Output fuse10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight20.4 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)
DesignationEN ISO 13849
Performance level (PL)e (In conjunction with suitable evaluating device)
Category4 (In conjunction with suitable evaluating device)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3 (In conjunction with suitable evaluating device)

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178/VDE 0160
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV:
between all current paths and housing
Safe isolation, reinforced insulation 6 kV:
between A1/A2, 11/12, 23/24, 71/72 and 33/34, 43/44, 53/54, 63/64
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.