PHOENIX CONTACT SACB-8/16-20,0PUR SCO SACB-8/16-20,0PUR SCO 1401305 PHOENIX CONTACT Sensor/actuator box View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SACB-8/16-20,0PUR SCO 1401305 PHOENIX CONTACT Sensor/actuator box

SACB-8/16-20,0PUR SCO

1401305

PHOENIX CONTACT

1 Pcs.

Sensor/actuator box

Cables > Passive sensor-actuator interface (with cable)
QUICKON Installation System (QPD)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey1401305
Packing unit1
GTIN4046356548731
Custom tariff number85444290

General

Rated voltage120 V
Max. operating voltage Umax135 V
Current carrying capacity per I/O signal2 A
Current carrying capacity per slot4 A
Total rated current12 A
Number of positions5
Number of slots8
Flammability rating according to UL 94V0

Ambient conditions

Degree of protectionIP65
IP67
IP69K
Ambient temperature (operation)-30 °C ... 90 °C
-40 °C ... 90 °C (for fixed installation)
-5 °C ... 80 °C (for flexible installation)

Master cable connection data

Connection methodFixed connection
Length of cable20 m

Insulation material

Housing materialPBT
Material of the moulding massPUR
Contact materialCu alloy
Contact surface materialgold-plated
Contact carrier materialPA
Material of threaded sleeveZinc die-cast
Material of threaded sleeve surfaceNickel-plated
O-ring materialNBR

Pin assignment

Slot/position = Wire color or connection1 / 4 (A) = WH
1 / 2 (B) = GY/PK
2 / 4 (A) = GN
2 / 2 (B) = RD/BU
3 / 4 (A) = YE
3 / 2 (B) = WH/GN
4 / 4 (A) = GY
4 / 2 (B) = BN/GN
5 / 4 (A) = PK
5 / 2 (B) = WH/YE
6 / 4 (A) = RD
6 / 2 (B) = YE/BN
7 / 4 (A) = BK
7 / 2 (B) = WH/GY
8 / 4 (A) = VT
8 / 2 (B) = GY/BN
1-8 / 1 (+ 120 V) = BN
1-8 / 3 (0 V) = BU
1-8 / 5 (PE) = GN/YE

Standards and Regulations

Flammability rating according to UL 94V0

Cable

Cable typePUR/PVC black
Cable type (abbreviation)PUR
Cable abbreviationLiYY11Y-HF
UL AWM style20549 (80°C/300 V)
Conductor cross section16x 0.5 mm² (Signal line)
3x 1 mm² (power line)
AWG signal line20
AWG power supply17
Conductor structure signal line28x 0.15 mm
Conductor structure, voltage supply56x 0.15 mm
Core diameter including insulation1.5 mm ±0.1 mm (Signal line)
2.1 mm ±0.1 mm (power line)
Wire colorsbrown, blue, green/yellow, white, green, yellow, gray, pink, red, black, violet, gray/pink, red/blue, white/green, brown/green, white/yellow, yellow/brown, white/gray, gray/brown
Overall twistWires twisted in layers
External sheath, colorblack RAL 9005
Inner sheath thickness≥ 0.15 mm
Outer sheath thickness≥ 0.76 mm
External cable diameter D10.5 mm ±0.2 mm
Minimum bending radius, fixed installation7.5 x D
Minimum bending radius, flexible installation10 x D
Number of bending cycles1500000
Minimum bending radius, drag chain applications10 x D
Traversing path2 m
Traversing rate2 m/s
Cable weight183.7 kg/km
Outer sheath, materialPUR
Material, inner sheathPVC
Material conductor insulationPVC
Conductor materialBare Cu litz wires
Nominal voltage, cable300 V
Test voltage, cable2000 V
Special propertiesSilicone-free
Flame resistanceaccording to DIN EN 50265
Resistance to oilaccording to VDE 0472 Part 803
Other resistanceHighly resistant to acids, alkaline solutions and solvents
Ambient temperature (operation)-40 °C ... 90 °C (cable, fixed installation)
-5 °C ... 80 °C (cable, flexible installation)

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.