PHOENIX CONTACT SACB-6/12-L-20,0PUR SCO P SACB-6/12-L-20,0PUR SCO P 1146339 PHOENIX CONTACT Sensor/actuator box, application: Standard, number of slot.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SACB-6/12-L-20,0PUR SCO P 1146339 PHOENIX CONTACT Sensor/actuator box, application: Standard, number of slot..

SACB-6/12-L-20,0PUR SCO P

1146339

PHOENIX CONTACT

20 Pcs.

Sensor/actuator box, application: Standard, number of slots: 6, number of positions: 5, coding: A - standard, slot assignment: Double, status display: yes, pnp; master cable connection: Fixed connection 180°, PUR/PVC, cable length: 20 m, shielding: no Sensor/actuator box, application: Standard, number of plug-in stations: 6, number of poles: 5, coding: A - standard, occupation of plug-in stations: Double, status indication: Yes, pnp; Main cable connection: Fixed connection 180°, PUR/PVC, cable length: 20 m, shielding: no

Cables > Passive sensor-actuator interface (with cable)
QUICKON Installation System (QPD)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey1146339
Packing unit1
GTIN4063151137373
Custom tariff number85444290

Drawings



Dimensional drawing

Dimensional drawing

Circuit diagram

Circuit diagram



Schematic diagram

Schematic diagram
M12 slot, socket, 5-pos.

Cable cross section

Cable cross section
PUR/PVC black [PUR]



Back to top

General

Rated voltage24 V DC
Max. operating voltage Umax30 V DC
Current carrying capacity per I/O signal2 A
Current carrying capacity per slot4 A
Total rated current12 A
Number of positions5
Number of slots6
NoteNOTE: Observe the permissible bending radii when laying conductors, since the degree of protection may be put in jeopardy if the bending forces are too high. Alleviate mechanical loads upstream of the connector, e.g. by using cable ties.
Unused slots are to be sealed off prior to commissioning. Suitable sealing elements are to be found under "Accessories".
Back to top

Ambient conditions

Degree of protectionIP65
IP67
Ambient temperature (operation)-25 °C ... 80 °C
-40 °C ... 90 °C (for fixed installation)
-5 °C ... 80 °C (for flexible installation)
Back to top

Local diagnostics function

Local diagnosticsSupply voltage Green LED
Status display I/O Yellow LED
Back to top

Master cable connection data

Connection methodFixed connection
Length of cable20 m
Tightening torque slot sensor/actuator cable0.4 Nm
Tightening torque of mounting screw for fixing the housing0.5 Nm
Back to top

Insulation material

Housing materialPBT
Material of the moulding massPUR
Contact materialCu alloy
Contact surface materialgold-plated
Contact carrier materialPA
Material of threaded sleevePBT
O-ring materialNBR
Back to top

Pin assignment

Slot/position = Wire color or connection1 / 4 (A) = WH
1 / 2 (B) = GY/PK
2 / 4 (A) = GN
2 / 2 (B) = RD/BU
3 / 4 (A) = YE
3 / 2 (B) = WH/GN
4 / 4 (A) = GY
4 / 2 (B) = BN/GN
5 / 4 (A) = PK
5 / 2 (B) = WH/YE
6 / 4 (A) = RD
6 / 2 (B) = YE/BN
1-6 / 1 (+ 24 V) = BN
1-6 / 3 (0 V) = BU
1-6 / 5 (PE) = GN/YE
Back to top

Standards and Regulations

Standards/specificationsM12 connector IEC 61076-2-101
Back to top

Cable

Cable typePUR/PVC black
Cable type (abbreviation)PUR
Cable abbreviationLiYY11Y-HF
UL AWM style20549
Conductor cross section12x 0.5 mm² (Signal line)
3x 1 mm² (power line)
AWG signal line20
AWG power supply17
Conductor structure signal line28x 0.15 mm
Conductor structure, voltage supply56x 0.15 mm
Core diameter including insulation1.5 mm ±0.1 mm (Signal line)
2.1 mm ±0.1 mm (power line)
Thickness, insulation≥ 0.15 mm (Inner sheath)
≥ 0.76 mm (Outer cable sheath)
Wire colorsbrown, blue, green/yellow, white, green, yellow, gray, pink, red, gray/pink, red/blue, white/green, brown/green, white/yellow, yellow/brown
Overall twistWires twisted in layers
External sheath, colorblack RAL 9005
External cable diameter D9.4 mm ±0.2 mm
Minimum bending radius, fixed installation7.5 x D
Minimum bending radius, flexible installation10 x D
Number of bending cycles1500000
Bending radius94 mm
Traversing path2 m
Traversing rate2 m/s
Cable weight150.9 kg/km
Outer sheath, materialPUR
Material, inner sheathPVC
Material conductor insulationPVC
Conductor materialBare Cu litz wires
Nominal voltage, cable300 V
Test voltage, cable2000 V
Special propertiesSilicone-free
Flame resistanceDIN EN 50265
Resistance to oilaccording to VDE 0472 Part 803
Other resistanceHighly resistant to acids, alkaline solutions and solvents
Ambient temperature (operation)-40 °C ... 90 °C (cable, fixed installation)
-5 °C ... 80 °C (cable, flexible installation)
Back to top

ETIM for 1146339 Sensors (EC002585)
Feature Name Feature Value
Length of the preassembled cable (EF007300) 20 m
Cable length configurable (EF007301) No
Number of sensor-/actuator-slots (EF006939) 6
Number of channels per connector slot (EF006885) 2
Number of poles sensor/actuator slots (EF007402) 5
Rated voltage (EF000228) 24 V
Operating voltage (EF003983) 24 V
Max. current carrying capacity per socket (EF004038) 2 A
Max. total current (EF004039) 12 A
Material of contact surface (EF004020) Gold
Material insulation body (EF007543) Polyamide (PA)
With LED indication (EF005950) Yes
With potential separation (EF003272) No
Connection for NPN-sensors (EF006817) No
Fix cable version suitable for cable guide chain (EF007461) No
Housing colour (EF000136) Other
Operating temperature (EF002393) -25 °C
Degree of protection (IP) (EF005474) IP65
Explosion safety category for gas (EF003997) Other
Explosion safety category for dust (EF003998) Other
Width (EF000008) 54 mm
Height (EF000040) 23 mm
Depth (EF000049) 123 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.