PHOENIX CONTACT SAC-5P- 1,5-920/M12FS OD SAC-5P- 1,5-920/M12FS OD 1413356 PHOENIX CONTACT Bus system cable SAC-5P- 1,5-920/M12FS OD 1413356 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SAC-5P- 1,5-920/M12FS OD 1413356 PHOENIX CONTACT Bus system cable SAC-5P- 1,5-920/M12FS OD 1413356

SAC-5P- 1,5-920/M12FS OD

1413356

PHOENIX CONTACT

50 Pcs.

Bus system cable - SAC-5P- 1,5-920/M12FS OD - 1413356 Bus System Cable, CANopen®, DeviceNet™, 5-pole, halogen-free PUR, violet RAL 4001, screened, free cable end, a Straight connection female M12, coding: A-coded, cable length: 1.5 m, for outdoor applications, with stainless steel knurling

Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Bus system cable, CANopen®, DeviceNet™, 5-position, PUR halogen-free, violet RAL 4001, shielded, free cable end, on Socket straight M12, A-coded, cable length: 1.5 m, for outdoor applications, with high-grade steel knurl

Key Commercial Data

Orderkey1413356
Packing unit1
GTIN4046356996556
Custom tariff number85444290

Dimensions

Length of cable1.5 m

Ambient conditions

Ambient temperature (operation)-40 °C ... 105 °C (Plug / socket)
-40 °C ... 85 °C (On sudden changes in temperature (according to IEC 60512-11-4))

General

Rated current at 40°C4 A
Rated voltage48 V AC
60 V DC
Number of positions5
Insulation resistance≥ 100 MΩ
CodingA - standard
Standards/regulationsM12 connector IEC 61076-2-101
Signal type/categoryCANopen®
DeviceNet™
Status displayNo
Degree of pollution3
Insertion/withdrawal cycles≥ 100

Material

Flammability rating according to UL 94V0
Contact materialCuSn
Contact surface materialNi/Au
Contact carrier materialPP
Material of grip bodyPP
Material, knurlsStainless steel
Sealing materialFPM

Standards and Regulations

Standard designationM12 connector
Standards/regulationsIEC 61076-2-101
Flammability rating according to UL 94V0

Cable

Cable typeCAN Bus/DeviceNet
Cable type (abbreviation)920
UL AWM style21198 (80°C/300 V)
Cable structure2xAWG24/19+2xAWG22/19
Conductor cross section2x 0.25 mm² (Data cable)
2x 0.34 mm² (Power supply)
1x 0.34 mm² (Drain wire)
AWG signal line24
AWG power supply22
Conductor structure signal line19x 0.13 mm
Conductor structure, voltage supply19x 0.15 mm
Core diameter including insulation1.95 mm ±0.05 mm (Data cable)
1.4 mm ±0.05 mm (Power supply)
Wire colorsRed-black, blue-white
Twisted pairs2 cores to the pair
Type of pair shieldingPlastic-coated aluminum foil, aluminum side outside
Overall twist2 pairs around a drain wire in the center to the core
ShieldingTinned copper braided shield
Optical shield covering80 %
External sheath, colorviolet RAL 4001
External cable diameter D6.7 mm ±0,3 mm
Minimum bending radius, fixed installation5 x D
Minimum bending radius, flexible installation10 x D
Number of bending cycles5000000
Bending radius70 mm
Minimum bending radius, drag chain applications10 x D
Traversing path4.5 m
Traversing rate3 m/s
Acceleration3 m/s²
Cable weight90 kg/km
Outer sheath, materialPUR
Material conductor insulationFoamed PE (Data cable)
PE (Power supply)
Conductor materialTin-plated Cu litz wires
Insulation resistance≥ 5 GΩ*km (Data cable)
≥ 5 GΩ*km (Power supply)
Loop resistance≤ 181.80 Ω/km (Data cable)
≤ 114.80 Ω/km (Power supply)
Cable capacitynom. 40 nF/km (Data cable)
Wave impedance120 Ω ±10 % (with 1 MHz)
Attenuation≤ 22.9 dB/km (with 1 MHz)
≤ 16.4 dB/km (At 500 kHz)
≤ 9.5 dB/km (At 125 kHz)
Nominal voltage, cable≤ 300 V (Peak value, not for high-power applications)
Test voltage Core/Core2000 V (50 Hz, 1 min.)
Test voltage Core/Shield2000 V (50 Hz, 1 min.)
Flame resistanceUL 1581, Sec. 1060 (FT-1)
IEC 60332-1
in accordance with ISO 6722-1 5.22 (UN ECE-R 118.01)
Halogen-freein accordance with DIN VDE 0472 part 815
according to IEC 60754-1
Other resistanceLow adhesion
Ambient temperature (operation)-40 °C ... 80 °C (cable, fixed installation)
-20 °C ... 80 °C (cable, flexible installation)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

eCl@ss

eCl@ss 5.127061800
eCl@ss 6.027279200
eCl@ss 7.027279218
eCl@ss 8.027279218
eCl@ss 9.027060311

ETIM

ETIM 4.0EC001855
ETIM 5.0EC001855
ETIM 6.0EC001855
ETIM 7.0EC001855

UNSPSC

UNSPSC 13.231251501

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.