PHOENIX CONTACT VAL-SEC-T2-380DC-P VAL-SEC-T2-380DC-P 2907880 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-380DC-P 2907880 PHOENIX CONTACT Type 2 surge protection plug

VAL-SEC-T2-380DC-P

2907880

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Replacement connector for surge protection device from the VALVETRAB SEC product line for DC power sources.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2907880
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 51 (C-4-2017)
GTIN4055626245058
Weight per Piece (excluding packing)61.600 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.4 mm
Width11.7 mm
Depth59.4 mm
Horizontal pitch0.6 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemDC
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN350 V DC ... 400 V DC
Maximum continuous voltage UC450 V DC
Residual current IPE≤ 350 µA DC
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Impulse discharge current (10/350) µs, charge0.5 As
Impulse discharge current (10/350) µs, specific energy0.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp1 kA
Short-circuit current rating ISCCR0.1 kA (without backup fuse)
6 kA (for 20 A gG/B backup fuse)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT551 V DC (5 s / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring20 A (gG / B at ISCCR> 200 A)
10 A (gG / B at ISCCR> 100 A)
Max. backup fuse with branch wiring20 A (gG / B at ISCCR> 200 A)
10 A (gG / B at ISCCR> 100 A)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV450 V DC
Nominal voltage400 V DC
Mode of protection(DC+) - G
(DC-) - G
Power distribution systemDC
Measured limiting voltage MLV1640 V
Nominal discharge current In20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values