PHOENIX CONTACT SAC-2P-100,0-913 SAC-2P-100,0-913 1416130 PHOENIX CONTACT Bus system cable View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SAC-2P-100,0-913 1416130 PHOENIX CONTACT Bus system cable

SAC-2P-100,0-913

1416130

PHOENIX CONTACT

1 Pcs.

Bus system cable Bus system cable, PROFIBUS PA (31.25 kBit/s), FOUNDATION Fieldbus (31.25 kBit/s), 2-pole, shielded, cable length: 100 m Bus system cable, PROFIBUS PA (31.25 kbps), FOUNDATION Fieldbus (31.25 kbps), 2-position, PVC, black, shielded, cable length: 100 m

Cables > Data and communication cable
Industrial Field Connectivity (IFC)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeData cable by the meter
Sensor typePROFIBUS PA
Number of positions2
Shieldedyes

Electrical properties
Transmission mediumCopper

Interfaces
Signal type/categoryPROFIBUS PA, 31.25 kbps
FOUNDATION Fieldbus, 31.25 kbps

Cable/line
Cable length100 m
PROFIBUS PA [913]
UL AWM Style2464
Number of positions2
Shieldedyes
Cable typePROFIBUS PA [913]
Conductor structure2xAWG18/7 + 1xAWG20/7
Signal speed0.77 c
Conductor structure signal line7x 0.40 mm
AWG signal line18
Conductor cross section2x 0.75 mm² (Signal line)
1x 0.5 mm² (Drain wire)
Wire diameter incl. insulation2.5 mm ±0.05 mm
External cable diameter7.80 mm
Outer sheath, materialPVC
External sheath, colorblack
Conductor materialTin-plated Cu litz wires
Material wire insulationFoamed PE
Single wire, colorred, green
Thickness, insulation0.65 mm
Thickness, outer sheath1.00 mm
Twisted pairs2 cores to the pair
Overall twistOne pair with one drain wire and fillers for core
Optical shield covering70 %
Max. conductor resistance20.5 Ω/km (Signal line)
9 Ω/km (shield)
Cable capacity80 nF/km (Line-line)
4 nF/km (Line-shield)
Cable impedance100 Ω ±20 % (At 31.25 kHz)
Nominal voltage, cable300 V
Tensile strength80 N
Flame resistanceaccording to IEC 60332-1
Resistance to oilAccording to ICEA S82-552
Other resistanceUV resistant (according to UL 1581, Section 1200)
Ambient temperature (operation)-30 °C ... 75 °C
Ambient temperature (installation)-5 °C ... 80 °C

ETIM for 1416130 Cable (EC003249)
Feature Name Feature Value
Conductor surface (EF010804) Other
Diameter conductor (EF001621) 2.5 mm
Nominal cross section conductor (EF000060) 0.75 mm²
Conductor category (EF001632) Class 2 = stranded
Number of cores (EF001792) 2
Material core insulation (EF000061) Other
Specification core insulation (EF011805) Other
Core identification (EF000067) Other
Screen over stranding element (EF001623) Foil + braiding
Stranding (EF003802) Other
Longitudinal water blocking cable (EF011011) No
Radial water blocking cable (EF011012) No
Suitable for underground installation (EF003689) No
Protective sheath (EF001691) None
Material outer sheath (EF001625) Polyvinyl chloride (PVC)
Specification material outer sheath (EF011806) Other
Colour outer sheath (EF001618) Black
Low smoke according to EN IEC 61034-2 (EF003799) No
Oil resistant according to EN IEC 60811-404 (EF009770) No
Outer diameter approx. (EF003921) 7.8 mm
Permitted cable outer temperature after assembling without vibration (EF001686) -30 °C
Category (EF001619) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.