View larger
VAL-SEC-T2-350-P
2905346
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2905346 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 42 (C-4-2017) |
| GTIN | 4046356948197 |
| Weight per Piece (excluding packing) | 58.700 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| TT | |
| Mode of protection | L-N |
| L-PEN | |
| Mounting type | on base element |
| Color | light grey RAL 7035 |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Surge protection fault message | optical |
| Nominal voltage UN | 240 V AC (TN) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 350 V AC |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA (in case of 315 A gG backup fuse) |
| 50 kA (in case of 200 A gG backup fuse) | |
| Voltage protection level Up | ≤ 1.5 kV |
| Residual voltage Ures | ≤ 1.5 kV (at In) |
| ≤ 1.3 kV (at 10 kA) | |
| ≤ 1.2 kV (at 5 kA) | |
| ≤ 1.1 kV (at 4 kA) | |
| ≤ 1 kV (at 2 kA) | |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 315 A (gG) |
| SPD Type | 1CA |
|---|---|
| Maximum continuous operating voltage MCOV | 350 V AC |
| Nom. voltage | 277 V AC |
| Mode of protection | L-N |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Voltage protection rating VPR | 1200 V |
| Nominal discharge current In | 20 kA |
| Short-circuit current rating (SCCR) | 50 kA |