PHOENIX CONTACT VAL-SEC-T2-N/PE-175-P VAL-SEC-T2-N/PE-175-P 2905356 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-N/PE-175-P 2905356 PHOENIX CONTACT Type 2 surge protection plug

VAL-SEC-T2-N/PE-175-P

2905356

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Replacement connector for surge arrester from the VALVETRAB SEC product line for the N-PE path.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905356
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 48 (C-4-2017)
GTIN4046356948227
Weight per Piece (excluding packing)49.300 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.4 mm
Width11.7 mm
Depth59.4 mm
Horizontal pitch0.6 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
Mode of protectionN-PE
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN120 V AC (TN - only N-PE)
120 V AC (TT - only N-PE)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC150 V AC
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Follow current interrupt rating Ifi100 A (150 V AC)
Voltage protection level Up≤ 0.95 kV
Residual voltage Ures≤ 0.4 kV (at In)
≤ 0.4 kV (at 10 kA)
≤ 0.4 kV (at 5 kA)
≤ 0.4 kV (at 4 kA)
≤ 0.4 kV (at 2 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 0.95 kV
TOV behavior at UT1200 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (N-G)150 V AC
Mode of protectionN-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (N-G)560 V
Nominal discharge current In(N-G)20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.