PHOENIX CONTACT FLT-SEC-P-T1-440/35-P FLT-SEC-P-T1-440/35-P 2905989 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FLT-SEC-P-T1-440/35-P 2905989 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-P-T1-440/35-P

2905989

PHOENIX CONTACT

1 Pcs.

Type 1 surge protection plug Replacement connector for lightning current arresters from the FLASHTRAB SEC PLUS 440 product series, for the L-N and L-PE sections.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905989
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 29 (C-4-2017)
GTIN4055626013282
Weight per Piece (excluding packing)241.750 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.6 mm
Width35.5 mm
Depth59.4 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationI / II
T1 / T2
EN typeT1 / T2
IEC power supply systemTT
Mode of protectionL-N
L-PE
L-PEN
N-PE (4+0)
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN400 V AC (TN)
400 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC440 V AC
Residual current IPE< 5 µA
Nominal discharge current In(8/20) µs35 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs, charge17.5 As
Impulse discharge current (10/350) µs, specific energy310 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp35 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.5 kV (at In)
TOV behavior at UT580 V AC (5 s / withstand mode)
800 V AC (120 min / withstand mode)
1640 V AC (200 ms / safe failure mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring400 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV440 V AC
Nom. voltage400 V AC
Mode of protectionL-N
L-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR1800 V
Nominal discharge current In20 kA
Short-circuit current rating (SCCR)25 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCN,N-dimethylacetamide 127-19-5
Lead 7439-92-1

Classifications


Product Datasheet