PHOENIX CONTACT FLT-SEC-H-T1-264/25-P FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-H-T1-264/25-P

2905968

PHOENIX CONTACT

1 Pcs.

Type 1 surge protection plug Replacement connector for lightning current arresters from the FLASHTRAB SEC HYBRID 264 product series, for the L-N and L-PEN sections.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905968
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 28 (C-4-2017)
GTIN4055626012032
Weight per Piece (excluding packing)335.780 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height113.4 mm
Width35.5 mm
Depth64.2 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationI / II
T1 / T2
EN typeT1 / T2
IEC power supply systemTN-C
Mode of protectionL-PEN
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Nominal discharge current In(8/20) µs25 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs, charge12.5 As
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp25 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 2.5 kV (at 50 kA)
≤ 1.2 kV (at 12.5 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 2.5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
460 V AC (120 min / withstand mode)
Response time tA≤ 100 ns

Additional technical data

Follow current interrupt rating Ifi100 kA
Short-circuit current rating ISCCR100 kA
Maximum discharge current Imax(8/20) µs100 kA (AS NZS 1768:2007)
Maximum continuous voltage UC275 V AC

Connection data

Connection methodpluggable

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


ETIM for 2905968 Earthing, lightning and surge protection (EC002496)
Feature Name Feature Value
Type of accessory/spare part (EF000215) Other
Accessory (EF013236) Yes
Spare part (EF013237) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.