View larger
REL-MR-110DC/1IC
1081621
PHOENIX CONTACT
10 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Degree of protection | RT II |
| Nominal input voltage UN | 110 V DC |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Typical input current at UN | 3.8 mA |
| Typical response time | 8 ms |
| Typical release time | 3 ms |
| Coil resistance | 28880 Ω ±10 % (20 °C) |
| Power dissipation for nominal condition | 0.42 W |
| Contact type | 1 N/O contact |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V (100 mA) |
| Min. switching current | 100 mA (at 12 V DC) |
| Maximum inrush current | 80 A (20 ms) |
| 130 A (peak, at capacitive load, 230 V AC, 24 μF) | |
| Limiting continuous current | 16 A |
| Interrupting rating (ohmic load) max. | 384 W (at 24 V DC) |
| 58 W (at 48 V DC) | |
| 48 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 80 W (at 220 V DC) | |
| 4000 VA (for 250 V AC) | |
| Switching capacity min. | 1200 mW |
| Test voltage relay winding/relay contact | 5 kV AC (50 Hz, 1 min.) |
|---|---|
| Operating mode | 100% operating factor |
| Mechanical service life | 3x 107cycles |
| Mounting position | any |
| Assembly instructions | Can be aligned without spacing (> 70 °C ≥ 2.5 mm) |
| Standards/regulations | EN 50178 |
|---|---|
| EN 61810-1 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation, reinforced insulation |
| Pollution degree | 3 |
| Overvoltage category | III |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |