PHOENIX CONTACT PT 2+1-S-48DC/FM PT 2+1-S-48DC/FM 2817958 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT 2+1-S-48DC/FM 2817958 PHOENIX CONTACT Type 3 surge protection device

PT 2+1-S-48DC/FM

2817958

PHOENIX CONTACT

1 Pcs.

Type 3 surge protection device Surge arrester for rail mounting as device protection for terminal equipment, fault signal on the connector and warning contact on the two-piece, plug-in base element. Execution: 48 V DC

Automation > Surge protection device for terminal equipment
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2817958
Packing unit10 pc
Catalog pagePage 72 (C-4-2017)
GTIN4017918574987
Weight per Piece (excluding packing)63.460 g
Custom tariff number85363090
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth65.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

EN typeT3
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
(L+) - (L-)
(L+/L-) - PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN48 V DC
Maximum continuous voltage UC60 V DC
Rated load current IL26 A (30 °C)
Residual current IPE≤ 10 µA
Nominal discharge current In(8/20) µs500 A
Combination wave UOC1 kV (2 Ω)
6 kV (12 Ω)
Voltage protection level Up≤ 120 V
Response time tA(L-N)≤ 1 ns
Response time tA(L-PE)≤ 1 ns
Short-circuit current rating ISCCR200 A (without backup fuse for Uc)
Max. backup fuse with branch wiring50 A (gG)
Maximum backup fuse for through wiring25 A (gG)

Indicator/remote signaling

Switching functionN/C contact
Operating voltage7 V DC ... 70 V DC (open collector)
Operating current5 mA DC ... 15 mA (open collector)
Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

Connection data

Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

Standards and Regulations

Standards/specificationsEN 61643-11 2012
IEC 61643-11 2011

Classifications


ETIM for 2817958 Earthing, lightning and surge protection (EC000942)
Feature Name Feature Value
Max. continuous voltage AC (EF004198) 60 V
Voltage protection level L-N (EF004236) 0.12 kV
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Max. conductor cross section solid (solid, stranded) (EF008827) 4 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 2.5 mm²
With remote signalling contact (EF000422) Yes
Signalling at the device (EF004241) Optic
Category type 3 (EF004231) Yes
Degree of protection (IP) (EF005474) IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.