PHOENIX CONTACT QUINT4-PS/1AC/24DC/20/+ QUINT4-PS/1AC/24DC/20/+ 2904617 PHOENIX CONTACT Primary-switched QUINT POWER supply for DIN rail mounting, w.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

QUINT4-PS/1AC/24DC/20/+ 2904617 PHOENIX CONTACT Primary-switched QUINT POWER supply for DIN rail mounting, w..

QUINT4-PS/1AC/24DC/20/+

2904617

PHOENIX CONTACT

1 Pcs.

Primary-switched QUINT POWER supply for DIN rail mounting, with selectable output characteristic curve and SFB Technology (selective fuse breaking), protective coating and integrated decoupling MOSFET, input: 1-phase, output: 24 V DC / 20 A QUINT POWER switched primary-switched power supply for rail mounting, with optional output characteristic curve and SFB Technology (Selective Fuse Breaking), protective paint and integrated decoupling Mosfet, input: single-phase, output: 24 V DC/20 A

Automation > DC-power supply
Power Supplies (PS)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2904617
Packing unit1 pc
Catalog pagePage 238 (C-4-2019)
GTIN4055626355085
Weight per Piece (excluding packing)1,640.000 g
Custom tariff number85044030
Country of originTH (Thailand)

Drawings



Block diagram

Block diagram

Diagram

Diagram



Diagram

Diagram

Diagram

Diagram



Dimensional drawing

Dimensional drawing

Schematic diagram

Schematic diagram



Back to top

Dimensions

Width70 mm
Height130 mm
Depth125 mm
Width with alternative assembly122 mm
Height with alternative assembly130 mm
Depth with alternative assembly73 mm
Back to top

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 75 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)-40 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)≤ 100 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2
Installation height≤ 5000 m (> 2000 m, observe derating)
Back to top

Input data

Nominal input voltage range100 V AC ... 240 V AC
Input voltage range100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -18 % ... +40 %
Dielectric strength maximum300 V AC 60 s
Frequency range (fN)50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Discharge current to PE< 3.5 mA
Current consumption6.8 A (100 V AC)
5.5 A (120 V AC)
2.8 A (230 V AC)
2.7 A (240 V AC)
Nominal power consumption520 VA
Inrush currenttyp. 10 A (at 25 °C)
Mains buffering timetyp. 36 ms (120 V AC)
typ. 36 ms (230 V AC)
Input fuse12 A (slow-blow, internal)
Recommended breaker for input protection10 A ... 16 A (Characteristic B, C, D, K or comparable)
Type of protectionTransient surge protection
Protective circuit/componentVaristor, gas-filled surge arrester
Back to top

Output data

Nominal output voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN)20 A
Static Boost (IStat.Boost)25 A
Dynamic Boost (IDyn.Boost)30 A (5 s)
Selective Fuse Breaking (ISFB)120 A (15 ms)
Connection in parallelYes, for redundancy and increased capacity
Connection in seriesyes
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)< 30 V DC (double protection incl. shutdown)
Control deviation< 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple< 30 mVPP(with nominal values)
Output power480 W
Typical response time300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition< 5 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max.< 38 W (120 V AC)
< 30 W (230 V AC)
Back to top

General

Net weight1.3 kg
Efficiencytyp. 92.7 % (120 V AC)
typ. 94.2 % (230 V AC)
Insulation voltage input/output4 kV AC (type test)
2 kV AC (routine test)
Protection classI
Degree of protectionIP20
MTBF (IEC 61709, SN 29500)> 868000 h (25 °C)
> 524000 h (40 °C)
> 239000 h (60 °C)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Assembly instructionsAlignable: horizontally 0 mm at Pout<50% PN, 5 mm at Pout≥50% PN, next to active components 15 mm, vertically 50 mm
Back to top

Connection data, input

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.10
Stripping length8 mm
Back to top

Connection data, output

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.10
Stripping length8 mm
Back to top

Connection data for signaling

Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm
Back to top

Standards

EMC requirements for noise immunityEN 61000-6-1
EN 61000-6-2
EMC requirements, power plantIEC 61850-3
EN 61000-6-5
HART FSK Physical Layer Test Specification ComplianceOutput voltage UOutcompliant
Standard - Safety of transformersEN 61558-2-16
Standard - Electrical safetyIEC 60950-1/VDE 0805 (SELV)
Standard - safety for equipment for measurement, control, and laboratory useIEC 61010-1
Standard – Safety extra-low voltageIEC 60950-1 (SELV)
EN 60204-1 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Explosive atmosphereIEC 60079-0
Mains variation/undervoltageSEMI F47-0706; EN 61000-4-11
Rail applicationsEN 50121-3-2
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
Back to top

Conformance/approvals

UL approvalsUL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
CSACAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
SIQBG (type approved)
Shipbuilding approvalDNV GL applied for
Back to top

EMC data

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Conducted noise emissionEN 55016
EN 61000-6-3 (Class B)
Noise emissionEN 55016
EN 61000-6-3 (Class B)
Harmonic currentsEN 61000-3-2
EN 61000-3-2 (Class A)
FlickerEN 61000-3-3
EN 61000-3-3
DNV GL conducted interferenceClass A
Additional textArea power distribution
DNV GL noise radiationClass B
Additional textBridge and deck area
Electrostatic dischargeEN 61000-4-2
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
Electromagnetic HF fieldEN 61000-4-3
Frequency range80 MHz ... 1 GHz
Test field strength20 V/m (Test Level 3)
Frequency range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
Frequency range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A
Fast transients (burst)EN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output4 kV (Test Level 4 - asymmetrical)
Signal4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A
Surge voltage load (surge)EN 61000-4-5
Inputtyp. 3 kV (Test Level 4 - symmetrical)
typ. 6 kV (Test Level 4 - asymmetrical)
Output1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A
I/O/Sasymmetrical
Frequency range0.15 MHz ... 80 MHz
Voltage10 V (Test Level 3)
CommentsCriterion A
Frequency16.7 Hz
50 Hz
60 Hz
Test field strength100 A/m
Additional text60 s
CommentsCriterion A
Frequency50 Hz
60 Hz
Test field strength1 kA/m
Additional text3 s
Frequency0 Hz
Test field strength300 A/m
Additional textDC, 60 s
Voltage dipsEN 61000-4-11
Voltage230 V AC
Frequency50 Hz
Voltage dip70 %
Number of periods0.5 / 1 / 25 / 30 periods
Additional textTest Level 2
CommentsCriterion A: 0.5 / 1 / 25 / 30 periods
Voltage dip40 %
Number of periods5 / 10 / 50 periods
Additional textTest Level 2
CommentsCriterion A
Voltage dip0 %
Number of periods0,5 / 1 / 5 / 50 / 250 periods
Additional textTest Level 2
CommentsCriterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic fieldEN 61000-4-9
Test field strength1000 A/m
CommentsCriterion A
Damped oscillating magnetic fieldEN 61000-4-10
Test field strength110 A/m
Test level 1100 kHz
Test field strength110 A/m
Test level 21 MHz
CommentsCriterion A
Attenuated sinusoidal oscillations (ring wave)EN 61000-4-12
Input2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A
Asymmetrical conducted disturbance variablesEN 61000-4-16
Test level 115 Hz 150 Hz (Test Level 4)
Voltage30 V 3 V
Test level 2150 Hz 1.5 kHz (Test Level 4)
Voltage3 V
Test level 31.5 kHz 15 kHz (Test Level 4)
Voltage3 V 30 V
Test level 415 kHz 150 kHz (Test Level 4)
Voltage30 V
Test level 516.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage30 V (Permanent)
Test level 6150 Hz 180 Hz (Test Level 4)
Voltage30 V (Permanent)
Test level 716.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage300 V (1 s)
CommentsCriterion A
Attenuated oscillating waveEN 61000-4-18
Input, output (test level 1)100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage1 kV
Input, output (test level 2)10 MHz
Voltage1 kV
Input, output (test level 1)100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage2.5 kV
Signals (test level 1)100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage1 kV
Signals (test level 2)100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage2.5 kV
CommentsCriterion A
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Criterion CTemporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
Back to top

Classifications

eCl@ss

eCl@ss 6.027049000
eCl@ss 7.027049002
eCl@ss 8.027049002
eCl@ss 9.027040701
Back to top

ETIM

ETIM 5.0EC002540
ETIM 6.0EC002540
ETIM 7.0EC002540
Back to top

ETIM for 2904617 Low-voltage industrial controls and switchgear (EC002540)
Feature Name Feature Value
Voltage type (supply voltage) (EF002991) AC
1st secondary output voltage (EF006792) 24 V
Max. output current 1 (EF008284) 30 A
Secondary voltage adjustable (EF007002) Yes
Nominal value output voltage 1 (EF009393) 24 V
Nominal value output current 1 (EF009396) 20 A
Short-circuit-proof (EF007332) Yes
Rated supply voltage AC 50 Hz (EF007076) 100 V
Rated supply voltage AC 60 Hz (EF007077) 100 V
Rated supply voltage DC (EF007078) 110 V
Output voltage stabilized (EF003092) Yes
Power consumption (EF000346) 520 VA
Power output (EF003034) 480 W
Stabilized (EF005302) Yes
Type of electric connection (EF003961) Screw connection
Suitable for rail mounting (EF003972) Yes
Wall mounting possible (EF003973) No
Modular version (EF001126) No
Built-in height (EF000332) 130 mm
Direct mounting possible (EF005689) No
Width (EF000008) 70 mm
Height (EF000040) 130 mm
Depth (EF000049) 125 mm
Suitable for safety functions (EF001597) Yes
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Degree of protection (IP) (EF005474) IP20
Degree of protection (NEMA) (EF011959) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.