QUINT4-PS/1AC/12DC/2.5/PT
2904605
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2904605 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 252 (C-4-2019) |
| GTIN | 4055626255736 |
| Weight per Piece (excluding packing) | 240.000 g |
| Custom tariff number | 85044030 |
| Country of origin | DE (Germany) |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
|---|---|
| 110 V DC ... 250 V DC -20 % ... +40 % | |
| Dielectric strength maximum | 300 V AC 60 s |
| Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 % |
| Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
| Current consumption | 0.44 A (100 V AC) |
| 0.35 A (120 V AC) | |
| 0.19 A (230 V AC) | |
| 0.2 A (240 V AC) | |
| Nominal power consumption | 32.8 VA |
| Inrush current | typ. 11.3 A (at 25 °C) |
| Mains buffering time | typ. 54 ms (120 V AC) |
| typ. 54 ms (230 V AC) | |
| Input fuse | 3.15 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C or comparable) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
| Nominal output voltage | 12 V DC |
|---|---|
| Setting range of the output voltage (USet) | 12 V DC ... 15 V DC (constant capacity) |
| Nominal output current (IN) | 2.5 A |
| Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
| Dynamic Boost (IDyn.Boost) | 4.5 A (≤ 60 °C (5 s)) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback voltage resistance | ≤ 25 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
| Control deviation | < 0.2 % (Static load change 10 % ... 90 %) |
| < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 30 mVPP(with nominal values) |
| Output power | 30 W |
| Typical response time | 500 ms |
| Maximum power dissipation in no-load condition | < 0.4 W (230 V AC) |
| < 0.5 W (120 V AC) | |
| Power loss nominal load max. | < 3.5 W (120 V AC) |
| < 3 W (230 V AC) |
| Net weight | 0.181 kg |
|---|---|
| Efficiency | typ. 89.5 % (120 V AC) |
| typ. 90.9 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 3 kV AC (routine test) | |
| Protection class | II |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1848000 h (25 °C) |
| > 1060000 h (40 °C) | |
| > 459000 h (60 °C) |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
| Standard - Safety of transformers | EN 61558-2-16 |
|---|---|
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| Standard - Safe isolation | IEC 61558-2-16 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL Listed UL 61010-1 |
|---|---|
| UL Listed UL 61010-2-201 | |
| UL 1310 Class 2 Power Units | |
| ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Harmonic currents | EN 61000-3-2 |
| EN 61000-3-2 (Class A) | |
| Flicker | EN 61000-3-3 |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 8 kV (Test Level 4) |
| Discharge in air | 15 kV (Test Level 4) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 20 V/m (Test Level X) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Output | 4 kV (Test Level X - asymmetrical) |
| Signal | 4 kV (Test Level X - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | EN 61000-4-5 |
| Input | 2 kV (Test Level 4 - symmetrical) |
| 4 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Signal | 0.5 kV (Test Level 2 - symmetrical) |
| Comments | Criterion A |
| I/O/S | asymmetrical |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Frequency | 16.67 Hz |
| 50 Hz | |
| 60 Hz | |
| Test field strength | 100 A/m |
| Additional text | 60 s |
| Comments | Criterion A |
| Frequency | 50 Hz |
| 60 Hz | |
| Test field strength | 1 kA/m |
| Additional text | 3 s |
| Frequency | 0 Hz |
| Test field strength | 300 A/m |
| Additional text | DC, 60 s |
| Voltage dips | EN 61000-4-11 |
| Voltage | 100 V AC |
| Frequency | 60 Hz |
| Voltage dip | 70 % |
| Number of periods | 0.5 / 1 / 30 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A |
| Voltage dip | 40 % |
| Number of periods | 5 / 10 / 50 periods |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Voltage dip | 0 % |
| Number of periods | 0.5 / 1 / 5 / 50 periods |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Pulse-shape magnetic field | EN 61000-4-9 |
| Test field strength | 1000 A/m |
| Comments | Criterion A |
| Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
| Input | 2 kV (symmetrical) |
| 4 kV (asymmetrical) | |
| Comments | Criterion A |
| Asymmetrical conducted disturbance variables | EN 61000-4-16 |
| Test level 1 | 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) |
| Voltage | 30 V (10 s) |
| Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 2) |
| Voltage | 300 V (1 s) |
| Comments | Criterion A |
| Attenuated oscillating wave | EN 61000-4-18 |
| Voltage | 1 kV (symmetrical) |
| 2.5 kV (asymmetrical) | |
| 1 kV (symmetrical) | |
| Comments | Criterion A |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| eCl@ss 5.1 | 27242213 |
|---|---|
| eCl@ss 6.0 | 27049000 |
| eCl@ss 7.0 | 27049002 |
| eCl@ss 8.0 | 27049002 |
| eCl@ss 9.0 | 27040701 |
| UNSPSC 13.2 | 39121004 |
|---|---|
| UNSPSC 18.0 | 39121004 |
| UNSPSC 19.0 | 39121004 |
| UNSPSC 20.0 | 39121004 |
| UNSPSC 21.0 | 39121004 |
| Feature Name | Feature Value |
|---|---|
| Voltage type (supply voltage) (EF002991) | AC/DC |
| 1st secondary output voltage (EF006792) | 12 V |
| Max. output current 1 (EF008284) | 4.5 A |
| Secondary voltage adjustable (EF007002) | Yes |
| Nominal value output voltage 1 (EF009393) | 12 V |
| Nominal value output current 1 (EF009396) | 2.5 A |
| Short-circuit-proof (EF007332) | Yes |
| Rated supply voltage AC 50 Hz (EF007076) | 100 V |
| Rated supply voltage AC 60 Hz (EF007077) | 100 V |
| Rated supply voltage DC (EF007078) | 110 V |
| Output voltage stabilized (EF003092) | Yes |
| Power consumption (EF000346) | 32.8 VA |
| Power output (EF003034) | 30 W |
| Stabilized (EF005302) | Yes |
| Type of electric connection (EF003961) | Other |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting possible (EF003973) | No |
| Modular version (EF001126) | No |
| Built-in height (EF000332) | 106 mm |
| Direct mounting possible (EF005689) | No |
| Width (EF000008) | 22.5 mm |
| Height (EF000040) | 106 mm |
| Depth (EF000049) | 90 mm |
| Suitable for safety functions (EF001597) | Yes |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Degree of protection (IP) (EF005474) | IP20 |
| Degree of protection (NEMA) (EF011959) | Other |