PHOENIX CONTACT TTC-6-1X2-M-24DC-UT-I TTC-6-1X2-M-24DC-UT-I 2906713 PHOENIX CONTACT Surge protection with integrated status indicator and knife di.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6-1X2-M-24DC-UT-I 2906713 PHOENIX CONTACT Surge protection with integrated status indicator and knife di..

TTC-6-1X2-M-24DC-UT-I

2906713

PHOENIX CONTACT

1 Pcs.

Surge protection with integrated status indicator and knife disconnection for a 2-wire floating signal circuit, e. g. 0(4)...20 mA current loop, HART-compatible. Surge protection with integrated status indication and blade interrupt for a potential-free 2-wire signal circuit, e.g. 0(4) current loop... 20 mA, EX e approval for zone 2, suitable for HART.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2906713
Packing unit1 pc
Catalog pagePage 118 (C-4-2019)
GTIN4055626134376
Weight per Piece (excluding packing)40.000 g
Custom tariff number85363010
Country of originDE (Germany)

Drawings



Diagram

Diagram

Dimensional drawing

Dimensional drawing



Pictogram

Pictogram

Circuit diagram

Circuit diagram



Back to top

Dimensions

Height105.8 mm
Width6.2 mm +0.1 mm
Depth83.5 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20
Back to top

General

Housing materialPBT
Flammability rating according to UL 94V-0
Colortraffic grey A RAL 7042
Mounting typeDIN rail: TH 35 - 7.5 mm
TypeDIN rail module, one-piece
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current600 mA (40 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 55 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 50 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-earth)≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 940 kHz
Capacity (line-line)typ. 2.2 nF
Resistance per path1.65 Ω ±20 %
Max. required back-up fuse630 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)≤ 700 ms
Pulse reset time (line-earth)≤ 1500 ms
Back to top

Additional technical data

Max. total discharge current Itotal max(8/20) µs20 kA (1x)
Back to top

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Back to top

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.027140201
eCl@ss 4.127130801
eCl@ss 5.027130801
eCl@ss 5.127130801
eCl@ss 6.027130800
eCl@ss 7.027130807
eCl@ss 8.027130807
eCl@ss 9.027130807
Back to top

ETIM

ETIM 3.0EC000943
ETIM 4.0EC000943
ETIM 5.0EC000943
ETIM 6.0EC000943
ETIM 7.0EC000943
Back to top

UNSPSC

UNSPSC 6.0130212010
UNSPSC 7.090139121610
UNSPSC 1139121610
UNSPSC 12.0139121610
UNSPSC 13.239121620
UNSPSC 18.039121620
UNSPSC 19.039121620
UNSPSC 20.039121620
UNSPSC 21.039121620
Back to top

ETIM for 2906713 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.