PHOENIX CONTACT PT 5-HF-24DC-ST PT 5-HF-24DC-ST 2906002 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT 5-HF-24DC-ST 2906002 PHOENIX CONTACT Surge protection device

PT 5-HF-24DC-ST

2906002

PHOENIX CONTACT

1 Pcs.

Surge protection device PT plug-in protection with AF protection circuit for 4 signal conductors. Rated voltage: 24 V DC

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2906002
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 160 (C-4-2017)
GTIN4055626013398
Weight per Piece (excluding packing)22.050 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height45 mm
Width17.7 mm
Depth52 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Altitude≤ 2000 m
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorblack
TypeMale
Number of positions5
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
VDE requirement classC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC28 V DC
Rated current450 mA (45°C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 5 µA (with PT 2X2-BE)
≤ 1 µA (with PT 2X2+F-BE)
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA (with PT 2X2+F-BE)
10 kA (with PT 2X2-BE)
Pulse discharge current Iimp(10/350) µs2.5 kA (with PT 2X2-BE)
2.5 kA (with PT 2X2+F-BE)
Total discharge current Itotal(8/20) µs20 kA
Nominal pulse current Ian (10/1000) µs (line-line)25 A
Voltage protection level Up(line-line)≤ 150 V (C1 - 1 kV/500 A)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 450 V (C2 - 10 kA)
≤ 50 V (C3 - 25 A)
Voltage protection level Up(line-earth)≤ 150 V (C1 - 1 kV/500 A)
≤ 700 V (C1 - 1 kV / 500 A with PT 2X2+F-BE)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 900 V (C2 - 10 kV / 5 kA with PT 2X2+F-BE)
≤ 450 V (C2 - 10 kA)
≤ 1000 V (C2 - 10 kA with PT 2X2+F-BE)
≤ 50 V (C3 - 25 A)
≤ 800 V (C3 - 25 A with PT 2X2+F-BE)
Voltage protection level Up(line-signalground)≤ 150 V (C1 - 1 kV/500 A)
≤ 150 V (C1 - 1 kV / 500 A with PT 2X2+F-BE)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 165 V (C2 - 10 kV / 5 kA with PT 2X2-BE)
≤ 450 V (C2 - 10 kA)
≤ 450 V (C2 - 10 kV / 5 kA with PT 2X2-BE)
≤ 50 V (C3 - 25 A)
≤ 50 V (C3 - 25 A with PT 2X2-BE)
Response time tA(line-line)≤ 500 ns
Response time tA(line-earth)≤ 500 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 13 MHz/100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 70 MHz
Capacity (line-line)typ. 23 pF
Resistance in series2.2 Ω ±10 %
Max. required back-up fuse500 mA (T)

Connection data

Connection methodScrew connection (in connection with the base element)
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Connection, equipotential bonding

Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12

Standards and Regulations

Standards/specificationsEN 61643-21/A2 2013
IEC 61643-21/A2 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


ETIM for 2906002 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 24 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.