View larger
PSR-SCP-24DC/ESD/4X1/30-SET35
1217839
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Product type | Safety relays |
| Product family | PSRclassic |
| Application | Emergency stop |
| Safety door | |
| Light grid | |
| Mechanical service life | approx. 107cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Maximum power dissipation for nominal condition | 1.8 W |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V |
| Rated surge voltage/insulation | 4 kV / basic insulation |
| General | |
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Typical input current at UN | 75 mA DC |
| Voltage at input/start and feedback circuit | approx. 24 V DC |
| Typical response time | 150 ms (Monitored/manual and auto-start) |
| Typical release time | 20 ms (Undelayed contacts) |
| 100 ms (delayed contacts) | |
| Typical release time range | 0.1 s ... 30 s |
| Recovery time | 330 ms (Restart) |
| 1 s (Electric torque) | |
| Protective circuit | Suppressor diode, 33 V DC |
| Max. permissible overall conductor resistance | 500 Ω (Input and reset circuit at UN) |
| Operating voltage display | Green LED |
| Status display | LED K1/K2 and K3(t)/K4(t), green |
| Contact switching type | 4 enabling current paths |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 15 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 25 mA |
| Sq. Total current | 120 A2(see to derating) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
| 288 W (48 V DC, τ = 0 ms) | |
| 90 W (110 V DC, τ = 0 ms) | |
| 88 W (220 V DC, τ = 0 ms) | |
| 1500 VA (250 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms) |
| 33 W (48 V DC, τ = 40 ms) | |
| 25 W (110 V DC, τ = 40 ms) | |
| 23 W (220 V DC, τ = 40 ms) | |
| Switching capacity min. | 0.4 W |
| Switching capacity (360/h cycles) | on request |
| Switching capacity (3600/h cycles) | 3 A (24 V (DC13)) |
| 3 A (230 V (AC15)) | |
| Output fuse | 10 A gL/gG NEOZED (N/O contact) |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Screw connection |
| Conductor cross section, rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Width | 22.5 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Housing material | Polyamide |
| Safety data | |
| Stop category | 0 |
| 1 | |
| Safety data: EN ISO 13849 | |
| Category | 4 |
| Performance level (PL) | e |
| Safety data | |
| Safety Integrity Level (SIL) | 3 |
| Safety data | |
| Safety Integrity Level (SIL) | 3 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 45 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | DIN EN 60947-1 |
| Mounting type | DIN rail mounting |
| Mounting position | any |
| Connection method | Screw connection |
| Feature Name | Feature Value |
|---|---|
| Model (EF000010) | Basic device |
| Suitable for rail mounting (EF003972) | Yes |
| With detachable clamps (EF003340) | Yes |
| Type of electric connection (EF003961) | Screw connection |
| Suitable for monitoring of position switches (EF007270) | Yes |
| Suitable for monitoring of emergency-stop circuits (EF007268) | Yes |
| Suitable for monitoring of valves (EF007272) | No |
| Suitable for monitoring of optoelectronic protection equipment (EF007269) | Yes |
| Suitable for monitoring of tactile sensors (EF007271) | No |
| Suitable for monitoring of magnetic switches (EF007266) | Yes |
| Suitable for monitoring of proximity switches (EF007267) | No |
| Evaluation inputs (EF008245) | Other |
| With start input (EF003342) | No |
| With muting function (EF004057) | No |
| With feedback circuit (EF003343) | Yes |
| Release-delay (EF001129) | 0.15 s |
| Number of outputs, safety related, undelayed, with contact (EF003344) | 0 |
| Number of outputs, safety related, delayed, with contact (EF003345) | 0 |
| Number of outputs, safety related, undelayed, semiconductors (EF003346) | 0 |
| Number of outputs, safety related, delayed, semiconductors (EF003347) | 0 |
| Number of outputs, signalling function, undelayed, with contact (EF003348) | 0 |
| Number of outputs, signalling function, delayed, with contact (EF003349) | 0 |
| Number of outputs, signalling function, undelayed, semiconductors (EF003350) | 0 |
| Number of outputs, signalling function, delayed, semiconductors (EF003351) | 0 |
| Stop category according to IEC 60204 (EF007498) | Other |
| With approval for BG BIA (EF004145) | No |
| With approval according to UL (EF001783) | No |
| Width (EF000008) | 22.5 mm |
| Height (EF000040) | 99 mm |
| Depth (EF000049) | 114.5 mm |