View larger
PSR-PLC21-2CO-24DC-PT
1480212
PHOENIX CONTACT
10 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Product type | Coupling relay |
| Product family | PLC-INTERFACE |
| Application | Forcibly guided contacts |
| Mechanical service life | approx. 107cycles |
| Relay type | Electromechanical relay in accordance with IEC/EN 61810 |
| Insulation characteristics: Air clearances and creepage distances between the power circuits | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Times | |
| Typ. starting time with Us | < 70 ms (when controlled via A1) |
| Typical release time | < 50 ms (on demand via A1) |
| Recovery time | 500 ms (following demand of the safety function) |
| Maximum power dissipation for nominal condition | 4.825 W (UB= 30 V, US= 24 V, IS= 30 mA, IL² = 37 A, Rcontact= 0.1 Ω) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
| Safe isolation, reinforced insulation 6 kV between 250 V load current paths and 24 V logic paths | |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 21.6 V DC ... 28.8 V DC |
| Rated control circuit supply voltage US | 24 V DC -10 % / +20 % |
| Rated control supply current IS | 30 mA |
| Inrush current | typ. 100 mA (Δt = 10 ms at Us) |
| Filter time | 1 ms (Test pulse width, high test pulse and low test pulse) |
| 1 s (Test pulse rate, high test pulse and low test pulse) | |
| Power consumption at UD | 650 mW (to US) |
| Protective circuit | Serial protection against polarity reversal; Suppressor diode, 38.6 V/600 W |
| Status display | 1 x green LED (PWR) |
| Relay: Relay outputs (11/12/14, 21/22/24) | |
| Output description | safety-related |
| Number of outputs | 2 |
| Contact switching type | 2 changeover contacts |
| Contact material | AgNi |
| Switching capacity | min. 150 mW (N/O contact / N/C contact) |
| Inrush current | max. 6 A (N/O contact) |
| max. 4 A (N/C contact) | |
| Switching capacity in accordance with IEC 60947-5-1 | 6 A (AC1, 230 V) |
| 3 A (AC15, 230 V) | |
| 6 A (DC1, 24 V, N/O contact) | |
| 4 A (DC1, 24 V, N/C contact) | |
| 3 A (DC13, 24 V, N/O contact) | |
| Limiting continuous current | 6 A (N/O contact, high demand) |
| 4 A (N/O contact, low demand) | |
| 4 A (N/C contact, high-demand) | |
| 2.4 A (N/C contact, low-demand) | |
| Sq. Total current | 37 A2(N/O contact, high-demand, observe derating) |
| 16 A2(N/C contact, high-demand, observe derating) | |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 107cycles |
| Output fuse | 6 A gL/gG |
| 4 A gL/gG (for low-demand applications) | |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 26 ... 14 |
| Stripping length | 8 mm |
| Operating voltage display | 1 x green LED (PWR) |
| Width | 14 mm |
| Height | 80 mm |
| Depth | 104 mm |
| Housing material | Polyamide |
| Safety data: EN ISO 13849 | |
| Category | 1 |
| Performance level (PL) | c |
| Safety data: IEC 61508 – High-demand for 1-channel wiring (1oo1 structure) | |
| Safety Integrity Level (SIL) | 2 |
| Safety data: IEC 61508 – Low-demand for 1-channel wiring (1oo1 structure) | |
| Safety Integrity Level (SIL) | 2 |
| Safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 2 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 60 °C (observe derating) |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average; 95% occasionally, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average; 95% occasionally, non-condensing) |
| Shock | 10g for Δt = 11 ms (continuous shock: 5g for Δt = 16 ms) |
| Vibration (operation) | 10 Hz ... 150 Hz, amplitude 0.75 mm, 1g |
| CE | |
| Identification | CE-compliant |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | IEC 60947-1 |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Mounting position | vertical or horizontal |
| Connection method | Push-in connection |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Other |
| Complete with socket (EF003359) | Yes |
| With detachable clamps (EF003340) | No |
| With LED indication (EF005950) | Yes |
| Rated control supply voltage DC (EF003980) | 21.6 V |
| Voltage type for actuating (EF008242) | DC |
| Number of contacts as normally closed contact (EF008255) | 0 |
| Number of contacts as normally open contact (EF008256) | 0 |
| Number of contacts as change-over contact (EF008257) | 0 |
| With forced-guided contacts (EF003357) | No |
| Nominal current (EF000001) | 0.03 A |
| Degree of protection (IP) (EF005474) | IP20 |
| Width (EF000008) | 14 mm |
| Height (EF000040) | 80 mm |
| Depth (EF000049) | 104 mm |