PSR-PC32-2NO-1NC-24-230UC-SC

2700581

PHOENIX CONTACT

1 Pcs.

Coupling relay Coupling relay for high and low demand applications SIL 3, couples digital signals to the periphery, wide input range of 24 V... 230 V, 2 trip circuits (1x up to 60 V, 1x up to 250 V), 1 acknowledgment circuit, "safe state off" applications, plug-in screw terminal block Coupling relay for SIL 3 high and low-demand applications, couples digital signals to the I/O, 24 V ... 230 V wide-range input, 2 enabling current paths (1x up to 60 V, 1x up to 250 V) 1 confirmation current path, safe state off applications, plug-in screw terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
Note on application
Note on applicationOnly for industrial use
Utilization restriction
CCCex noteUse in potentially explosive areas is not permitted in China.

Product properties
Product typeCoupling relay
Product familyPSRmini
ApplicationSafe switch off
High demand
Low demand
Ex
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Data management status
Article revision04
Times
Typical response time< 100 ms (with Uswhen controlled via A1)
Typical release time< 200 ms (with Uswhen controlled via A1)
Recovery time< 500 ms

Electrical properties
Maximum power dissipation for nominal condition5.7 W (at IL² = 72 A²)
Nominal operating mode100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between all current paths and housing
Safe isolation, reinforced insulation 2.5 kV between (93/94) and (31/32, 24V/GND)
Safe isolation, reinforced insulation 6 kV:
between (A1/A2) and (13/14) and (31/32, 24V/GND)
between (A1/A2) and (93/94)
between (13/14) and (93/94)
Supply
DesignationA1/A2
Rated control circuit supply voltage US24 V AC/DC ... 230 V AC/DC -15 % ... +10 %
Rated control supply current IS75 mA (24 V DC)
34 mA (48 V DC)
97 mA (42 V AC)
28 mA (120 V AC)
16 mA (230 V AC)
Power consumption at US1.8 W (with DC)
2.1 W (with AC)
Apparent powertyp. 4.1 VA
Inrush currenttyp. 16 A (Δt s)
< 5 mA (at terminal blocks 24V/GND at UD)
Filter time10 ms (24 V DC, A1 in the event of voltage dips at Us)
max. 1.5 ms (at A1-A2; test pulse width; at 24 V DC)
7.5 ms (at A1-A2; test pulse rate; at 24 V DC)
Test pulse rate = 5 x Test pulse width
Protective circuitSurge protection; Varistor 275 V
Supply
Designation24V/GND
Diagnostic supply voltage UD24 V DC -15 % / +10 %
Input current at UD< 5 mA (at terminal blocks 24V/GND at UD)
Protective circuitSurge protection; 33 V suppressor diode
Reverse polarity protection

Output data
Relay: Enabling current path
Output descriptionsafety-related N/O contacts
Number of outputs2 (undelayed)
Contact switching type2 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 12 V AC/DC
max. 250 V AC/DC (13/14, observe the load curve)
max. 60 V AC/DC (93/94, observe the load curve)
Switching capacitymin. 60 mW
Inrush currentmin. 3 mA
max. 6 A
Switching capacity (360/h cycles)4 A (24 V (DC13))
5 A (230 V (AC 15))
Limiting continuous current6 A (observe derating)
Sq. Total current72 A2(observe derating)
Switching frequencymax. 1 Hz
Mechanical service life10x 106cycles
Output fuse6 A gL/gG
4 A gL/gG (for low-demand applications)
Relay: Confirmation current path
Output descriptionSafety-related N/C contacts
Number of outputs1 (undelayed)
Contact switching type1 confirmation current path
Contact materialAgCuNi, + Au
Switching voltagemin. 3.3 V AC/DC
max. 26.4 V DC
Switching capacitymin. 3.3 mW
Inrush currentmin. 1 mA
max. 100 mA
Limiting continuous current100 mA
Output fuse150 mA fast blow

Connection data
Connection technology
pluggableyes
Conductor connection
Connection methodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3

Signaling
Status display1 x LED (green), 1 x LED (yellow)
Operating voltage display1 x yellow LED

Dimensions
Width17.5 mm
Height112.2 mm
Depth114.5 mm

Material specifications
Color (Housing)yellow (RAL 1018)
Housing materialPolyamide

Characteristics
Safety data
Stop category0
Safety data: EN 50156-2
Safety Integrity Level (SIL)3 (Reference IEC 61508)
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL)3 (
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL)3 (

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Ambient temperature (operation)-40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g

Approvals
ATEX
Identification II 3G  Ex ec nC IIC T4 Gc
CertificateUL 22 ATEX 2912X
IECEx
IdentificationEx ec nC IIC T4 Gc
CertificateIECEx UL 22.0037X
UL, USA/Canada
IdentificationcULus
CertificateE140324
UL Ex, USA / Canada
IdentificationClass I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
Class I, Div. 2, Groups A, B, C, D, T4
CertificateE360692
CE
IdentificationCE-compliant
Environmental simulation test
IdentificationG3
CertificateISA-S71.04
CCC / China-Ex
IdentificationEx ec nC IIC T4 Gc
Certificate2022122304115695

Standards and regulations
Air clearances and creepage distances between the power circuits
Standards/regulationsEN 60664-1, EN 60079-7, EN 60079-15

Mounting
Mounting typeDIN rail mounting
Assembly noteSee derating curve
Mounting positionvertical or horizontal

ETIM for 2700581 Relays (EC001449)
Feature Name Feature Value
Model (EF000010) Basic device
Suitable for rail mounting (EF003972) Yes
With detachable clamps (EF003340) Yes
Type of electric connection (EF003961) Screw connection
Suitable for monitoring of emergency-stop circuits (EF007268) No
Suitable for monitoring of valves (EF007272) No
Suitable for monitoring of optoelectronic protection equipment (EF007269) No
Suitable for monitoring of tactile sensors (EF007271) No
Suitable for monitoring of magnetic switches (EF007266) No
Suitable for monitoring of proximity switches (EF007267) No
Evaluation inputs (EF008245) Other
With start input (EF003342) No
With muting function (EF004057) No
With feedback circuit (EF003343) No
Release-delay (EF001129) 0.1 s
Number of outputs, safety related, undelayed, with contact (EF003344) 0
Number of outputs, safety related, delayed, with contact (EF003345) 0
Number of outputs, safety related, undelayed, semiconductors (EF003346) 0
Number of outputs, safety related, delayed, semiconductors (EF003347) 0
Number of outputs, signalling function, undelayed, with contact (EF003348) 0
Number of outputs, signalling function, delayed, with contact (EF003349) 0
Number of outputs, signalling function, undelayed, semiconductors (EF003350) 0
Number of outputs, signalling function, delayed, semiconductors (EF003351) 0
Stop category according to IEC 60204 (EF007498) Other
With approval for BG BIA (EF004145) No
With approval according to UL (EF001783) No
Width (EF000008) 17.5 mm
Height (EF000040) 112.2 mm
Depth (EF000049) 114.5 mm