PHOENIX CONTACT PSR-MC38-2NO-1DO-24DC-SC PSR-MC38-2NO-1DO-24DC-SC 1009831 PHOENIX CONTACT Safety relay for emergency stop, safety doors and light gri.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-MC38-2NO-1DO-24DC-SC 1009831 PHOENIX CONTACT Safety relay for emergency stop, safety doors and light gri..

PSR-MC38-2NO-1DO-24DC-SC

1009831

PHOENIX CONTACT

1 Pcs.

Safety relay for emergency stop, safety doors and light grids up to SILCL 3, Cat. 4, PL e, 1- or 2-channel operation, automatic or manual, monitored start, 2 enabling current paths, 1 signal output, TBUS interface, U Safety relay for emergency stop, protection doors and light barrier up to SIL 3, cat. 4, PL e, 1 or 2 channel operation, automatic or manual, monitored start, 2 trip circuits, 1 message output, TBUS interface, US = 24 V DC, plug-in screw terminal

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey1009831
Packing unit1 pc
Catalog pagePage 223 (C-6-2019)
GTIN4055626482705
Weight per Piece (excluding packing)200.000 g
Custom tariff number85371098
Country of originDE (Germany)

Drawings



Block diagram

Circuit diagram

Circuit diagram



Back to top

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width22.5 mm
Height112.2 mm
Depth114.5 mm
Back to top

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)
Back to top

Power supply

DesignationA1/A2
Rated control circuit supply voltage US24 V DC -15 % / +10 % (provide external protection)
Rated control supply current IStyp. 75 mA
Power consumption at UStyp. 1.8 W
Inrush current< 4 A (Δt = 3 ms at Us)
Filter time20 ms (at A1 in the event of voltage dips at Us)
Protective circuitSerial protection against polarity reversal Suppressor diode
Back to top

Digital inputs

Input nameSensor circuit
S10, S12, S13, S22
Description of the inputsafety-related sensor inputs
NPN (S10, S12, S13), PNP (S22)
Number of inputs4
Input voltage range "1" signal20.4 V DC ... 26.4 V DC
Inrush current< 40 mA (typ. with USat S10)
< 300 mA (typ. with USat S12, Δt = 150 ms)
< 3 mA (Typically with USat S13)
> -300 mA (Typically with USat S22, Δt = 150 ms)
Current consumption40 mA (typ. with USat S10)
45 mA (Typically with USat S12)
3 mA (Typically with USat S13)
-35 mA (Typically with USat S22, Δt = 150 ms)
Filter time2 ms (At S10, S12, S13; test pulse width of low test pulses)
1 ms (At S10, S12, S13; test pulse rate of low test pulses)
No brightness test pulses / high test pulses permitted.
Max. permissible overall conductor resistance50 Ω
Concurrence input 1/2
Protective circuit/componentSuppressor diode
Input nameStart circuit
Y1, S34, S35
Description of the inputnon-safety-related
NPN
Number of inputs3
Input voltage range "1" signal20.4 V DC ... 26.4 V DC
Inrush current< 60 mA (Typically with USat Y1, Δt = 150 ms)
< 270 mA (Typically with USat S34, Δt = 15 ms)
< 80 mA (Typically with USat S35, Δt = 25 ms)
Current consumptiontyp. 10 mA (Typically with USat Y1)
typ. 34 µA (Typically with USat S35)
Max. permissible overall conductor resistance50 Ω
Protective circuit/componentSuppressor diode
Back to top

Relay outputs: enabling current path

Output nameEnabling current path
13/14, 23/24
Output descriptionsafety-related N/O contacts
2 NO contacts each in series, without delay, floating
Number of outputs2 (undelayed)
Contact type2 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 10 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Limiting continuous current6 A
Inrush currentmin. 10 mA
max. 6 A
Sq. Total current72 A2(observe derating)
Switching capacitymin. 100 mW
Switching frequencymax. 0.5 Hz
Mechanical service life10x 106cycles
Switching capacity according to IEC 60947-5-15 A (24 V (DC13))
5 A (250 V (AC15))
Output fuse10 A gL/gG
4 A gL/gG (for low-demand applications)
Back to top

Alarm outputs

DesignationY30
Output descriptionPNP
non-safety-related
Number of outputs1
Voltageapprox. 23.9 V DC (Us- 0.1 V)
Currentmax. 100 mA
Maximum inrush current500 mA (Δt = 1 ms at Us)
Protective circuit/componentSuppressor diode
Back to top

Times

Typical pickup time at US200 ms (when controlled via A1)
Typical response time at US200 ms (automatic start)
30 ms (manual, monitored start)
Typical release time at US25 ms (when actuation is via the sensor circuit)
60 ms (when controlled via A1)
Restart time< 1 s (Boot time)
Recovery time< 500 ms
Back to top

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight169.38 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow
Operating voltage display1 x green LED
Status display4 x green LEDs
Back to top

Connection data

Connection methodScrew connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3
Torque0.5 Nm ... 0.6 Nm
Back to top

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3
DesignationEN ISO 13849
Performance level (PL)e
Category4 (5 A DC13; 5 A AC15; 8760 switching cycles/year)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3
Back to top

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178
Rated insulation voltage250 V
250 V
Rated surge voltage/insulationSafe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24)
Basic insulation 4 kV between all current paths and housing
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 8.027371819
eCl@ss 9.027371819
Back to top

ETIM

ETIM 5.0EC001449
ETIM 6.0EC001449
ETIM 7.0EC001449
Back to top

ETIM for 1009831 Relays (EC001449)
Feature Name Feature Value
Model (EF000010) Basic device
Suitable for rail mounting (EF003972) Yes
With detachable clamps (EF003340) Yes
Type of electric connection (EF003961) Screw connection
Suitable for monitoring of position switches (EF007270) Yes
Suitable for monitoring of emergency-stop circuits (EF007268) Yes
Suitable for monitoring of valves (EF007272) No
Suitable for monitoring of optoelectronic protection equipment (EF007269) Yes
Suitable for monitoring of tactile sensors (EF007271) No
Suitable for monitoring of magnetic switches (EF007266) Yes
Suitable for monitoring of proximity switches (EF007267) No
Evaluation inputs (EF008245) Other
With start input (EF003342) No
With muting function (EF004057) No
With feedback circuit (EF003343) Yes
Release-delay (EF001129) 0.2 s
Number of outputs, safety related, undelayed, with contact (EF003344) 2
Number of outputs, safety related, delayed, with contact (EF003345) 0
Number of outputs, safety related, undelayed, semiconductors (EF003346) 0
Number of outputs, safety related, delayed, semiconductors (EF003347) 0
Number of outputs, signalling function, undelayed, with contact (EF003348) 0
Number of outputs, signalling function, delayed, with contact (EF003349) 0
Number of outputs, signalling function, undelayed, semiconductors (EF003350) 0
Number of outputs, signalling function, delayed, semiconductors (EF003351) 0
Stop category according to IEC 60204 (EF007498) Other
With approval for BG BIA (EF004145) No
With approval according to UL (EF001783) No
Width (EF000008) 22.5 mm
Height (EF000040) 112.2 mm
Depth (EF000049) 114.5 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.