PHOENIX CONTACT PT 2X2-HF-24 DC-ST PT 2X2-HF-24 DC-ST 2839729 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT 2X2-HF-24 DC-ST 2839729 PHOENIX CONTACT Surge protection plug

PT 2X2-HF-24 DC-ST

2839729

PHOENIX CONTACT

10 Pcs.

Surge protection plug PT plug-in protection with HF (high frequency) protection circuit for two two-conductor signal circuits without ground potential. Rated voltage: 24 V DC

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2839729
Packing unit10 pc
Catalog pagePage 161 (C-4-2017)
GTIN4017918607210
Weight per Piece (excluding packing)22.320 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height45 mm
Width17.7 mm
Depth52 mm
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
Mounting typeon base element
TypeMale
Number of positions5
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
VDE requirement classC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC28 V DC
19.8 V AC
Rated current450 mA (45°C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 4 µA (with PT 2X2-BE)
≤ 1 µA (with PT 2X2+F-BE)
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Max. discharge current Imax(8/20) µs maximum (line-line)10 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA
Nominal pulse current Ian (10/1000) µs (line-line)30 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 120 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 450 V
≤ 1 kV (with PT 2X2+F-BE)
Output voltage limitation at 1 kV/µs (line-line) static≤ 45 V
Output voltage limitation at 1 kV/µs (line-signalground) static≤ 450 V
Residual voltage at In(line-line)≤ 40 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 50 V
Voltage protection level Up(line-line)≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth)≤ 450 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 500 ns
Response time tA(line-earth)≤ 500 ns
Input attenuation aE, sym.0.2 dB (≤ 5 MHz)
Input attenuation aE, asym.
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 70 MHz
Capacity (line-line)typ. 30 pF
Resistance in series2.2 Ω
Surge protection fault messagenone
Max. required back-up fuse500 mA (T)
Impulse durability (line-line)C2 - 10 kV/5 kA
Impulse durability (line-earth)C2 - 10 kV/5 kA
D1 - 2.5 kA

Connection data

Connection methodScrew connection (in connection with the base element)
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2000

Classifications


ETIM for 2839729 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 24 V

Product Datasheet