View larger
TRIO-PS-2G/3AC/24DC/10
2903154
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2903154 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 223 (C-4-2017) |
| GTIN | 4046356960953 |
| Weight per Piece (excluding packing) | 1,175.500 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
| Nominal input voltage range | 3x 400 V AC ... 500 V AC |
|---|---|
| 2x 400 V AC ... 500 V AC | |
| Input voltage range | 3x 400 V AC ... 500 V AC -20 % ....+15 % |
| 2x 400 V AC ... 500 V AC -10 % ... +15 % | |
| AC frequency range | 50 Hz ... 60 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 3x 0.6 A (400 V AC) |
| 3x 0.6 A (500 V AC) | |
| 2x 1.1 A (400 V AC) | |
| 2x 1.1 A (500 V AC) | |
| Nominal power consumption | 451.7 VA |
| Inrush surge current | ≤ 26 A (typical) |
| Mains buffering | typ. 10 ms (400 V AC) |
| typ. 20 ms (500 V AC) | |
| Input fuse | 3.15 A (internal (device protection), slow-blow) |
| Choice of suitable circuit breakers | 6 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.58 |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A |
| Dynamic Boost (IDyn.Boost) | 15 A (5 s) |
| Derating | > 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Output overvoltage protection | ≤ 30 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | ≤ 20 mVPP |
| Output power | 240 W |
| Typical response time | < 1 s |
| Maximum power dissipation in no-load condition | < 1.1 W (400 V AC) |
| Power loss nominal load max. | < 22 W (480 V AC) |
| Net weight | 0.9 kg |
|---|---|
| Efficiency | > 92 % (at 400 V AC and nominal values) |
| Insulation voltage input/output | 3 kV AC (type test) |
| 1.5 kV AC (routine test) | |
| Protection class | I (in closed control cabinet) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 2100000 h (25 °C) |
| > 1200000 h (40 °C) | |
| > 590000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | Immunity according to EN 61000-6-2 (industrial) |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Conducted noise emission | EN 55016 EN 61000-6-4 (Class A) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 4g, 90 min. | |
| Rail applications | EN 50121-4 |
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Voltage type (supply voltage) (EF002991) | AC |
| 1st secondary output voltage (EF006792) | 24 V |
| Max. output current 1 (EF008284) | 15 A |
| Secondary voltage adjustable (EF007002) | Yes |
| Nominal value output voltage 1 (EF009393) | 24 V |
| Nominal value output current 1 (EF009396) | 10 A |
| Short-circuit-proof (EF007332) | Yes |
| Rated supply voltage AC 50 Hz (EF007076) | 320 V |
| Rated supply voltage AC 60 Hz (EF007077) | 320 V |
| Output voltage stabilized (EF003092) | Yes |
| Power consumption (EF000346) | 451.7 VA |
| Power output (EF003034) | 240 W |
| Stabilized (EF005302) | Yes |
| Type of electric connection (EF003961) | Other |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting possible (EF003973) | No |
| Modular version (EF001126) | No |
| Built-in height (EF000332) | 130 mm |
| Direct mounting possible (EF005689) | No |
| Width (EF000008) | 42 mm |
| Height (EF000040) | 130 mm |
| Depth (EF000049) | 160 mm |
| Suitable for safety functions (EF001597) | Yes |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Degree of protection (IP) (EF005474) | IP20 |
| Degree of protection (NEMA) (EF011959) | Other |