View larger
RIF-2-RPT-LV-230AC/2X21
2903310
PHOENIX CONTACT
10 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Width | 31 mm |
|---|---|
| Height | 96 mm |
| Depth | 75 mm |
| Ambient temperature (operation) | -40 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Nominal input voltage UN | 230 V AC |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Mains frequency | 50 Hz |
| 60 Hz | |
| Typical input current at UN | 6.5 mA |
| Typical response time | 5 ms ... 15 ms |
| Typical release time range | 5 ms ... 20 ms |
| Coil voltage | 230 V AC |
| Protective circuit | Varistor |
| Operating voltage display | Yellow LED |
| Contact type | 2 PDT |
|---|---|
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (At 24 mA) |
| Min. switching current | 5 mA (at 24 V) |
| Maximum inrush current | 30 A (20 ms, N/O contact) |
| Limiting continuous current | 8.5 A (see diagram) |
| Interrupting rating (ohmic load) max. | 204 W (at 24 V DC) |
| 124 W (at 48 V DC) | |
| 108 W (at 60 V DC) | |
| 52 W (at 110 V DC) | |
| 48 W (at 220 V DC) | |
| 2125 VA (for 250 V AC) | |
| Switching capacity in acc. with DIN VDE 0660/IEC 60947 | 2 A (at 24 V, DC13) |
| 0.22 A (at 120 V, DC13) | |
| 0.11 A (at 250 V, DC13) | |
| 3 A (at 120 V, AC15) | |
| 1.5 A (at 240 V, AC15) |
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) | |
| 0.14 mm² ... 1.5 mm² (Ferrules without plastic sleeve) | |
| Conductor cross section AWG | 26 ... 16 |
| Test voltage relay winding/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
|---|---|
| Test voltage relay contact/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | IP20 (Relay socket) |
| RT I (Relay) | |
| Mechanical service life | Approx. 2 x 107cycles |
| Standards/regulations | DIN EN 50178 |
| IEC 62103 | |
| Rated insulation voltage | 250 V AC |
| Pollution degree | 2 |
| Overvoltage category | III |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |