Type 2 surge arrester Plug-in surge arrester according to type 2/class II, for three-phase power supply networks with PE and N routing combined in one conductor (4-conductor system: L1, L2, L3, PEN).

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905344
Packing unit1 pc
Catalog pagePage 46 (C-4-2017)
GTIN4046356947978
Weight per Piece (excluding packing)314.700 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height89.9 mm
Width37.3 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
Mode of protectionL-PEN
Mounting typeDIN rail: 35 mm
Colorlight grey RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions3
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240/415 V AC (TN-C)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Rated load current IL40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA (in case of 315 A gG backup fuse)
50 kA (in case of 200 A gG backup fuse)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring315 A (gG)

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 6 mm²

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-L)700 V AC
Maximum continuous operating voltage MCOV (L-N)350 V AC
Nom. voltage277/480 V AC
Mode of protectionL-L
L-N
Power distribution systemWye
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-L)3280 V
Measured limiting voltage MLV (L-N)2000 V
Nominal discharge current In(L-L)20 kA
Nominal discharge current In(L-N)20 kA

UL connection data

Conductor cross section AWG14 ... 2 (solid)
14 ... 4 (flexible)
Tightening torque40 lbf-in. ... 50 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


ETIM for 2905344 Earthing, lightning and surge protection (EC000941)
Feature Name Feature Value
System configuration DC (EF009926) No
System configuration IT (EF009927) No
System configuration TN (EF009928) No
System configuration TN-C (EF009929) Yes
System configuration TN-C-S (EF009933) No
System configuration TN-S (EF009930) No
System configuration TT (EF009931) No
System configuration other (EF009932) No
Nominal discharge surge current (8/20) (EF004214) 20 kA
Max. discharge surge current (8/20) (EF012274) 40 kA
Max. continuous voltage AC (EF004198) 350 V
Voltage protection level L-N (EF004236) 1.5 kV
Max. overcurrent protection device, parallel connection (fuse) (EF015962) 315 A
Max. overcurrent protection device, series connection (fuse) (EF015963) 40 A
Short-circuit breaking capacity (Isccr) (EF012627) 50 kA
Integrated backup fuse (EF008797) Yes
Leakage-current free (EF016002) No
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) Other
Max. conductor cross section solid (solid, stranded) (EF008827) 2.5 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 16 mm²
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) Yes
Degree of protection (IP) (EF005474) IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.