PHOENIX CONTACT PLT-SEC-T3-BE-FM-UT PLT-SEC-T3-BE-FM-UT 2907924 PHOENIX CONTACT Type 3 surge protection base element View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLT-SEC-T3-BE-FM-UT 2907924 PHOENIX CONTACT Type 3 surge protection base element

PLT-SEC-T3-BE-FM-UT

2907924

PHOENIX CONTACT

1 Pcs.

Type 3 surge protection base element Plug-in protection base element from the PLT-SEC-...-UT/PT product series with remote indication contact.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2907924
Packing unit10 pc
GTIN4055626257709
Weight per Piece (excluding packing)48.000 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height93.4 mm
Width17.7 mm
Depth51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 ... 500 Hz / 2.5 h / X, Y, Z)

General

EN typeT2 / T3
IEC power supply systemTN-S
TT
Number of portsOne
Mounting typeDIN rail: 35 mm
Colorlight gray RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageRemote indication contact

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL26 A (at 30 °C)
Short-circuit current rating ISCCR10 kA AC
Max. backup fuse with branch wiringdepends on the plug used
Maximum backup fuse for through wiring25 A (gG / B / C)

Additional technical data

Short-circuit current rating ISCCRmax. 5 kA DC (depends on the plug used)
Maximum continuous voltage UC240 V DC

Indicator/remote signaling

Switching functionPDT contact
Operating voltage250 V AC
125 V DC (200 mA DC)
Operating current0.5 A AC
0.5 A DC (75 V DC)
Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section AWG30 ... 12
Screw threadM3
Tightening torque0.5 Nm
Stripping length10 mm

Connection data

Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.5 Nm
Stripping length10 mm

UL specifications

SPD TypeACC
Nominal voltage240 V DC
Rated load current IL20 A
Power distribution systemSingle phase
DC
Nominal frequency50/60 Hz

UL indicator/remote signaling

Operating voltage250 V AC (0.5 A)
12 V DC (4 A)
24 V DC (2 A)
48 V DC (1 A)
Tightening torque5 lbf-in. ... 7 lbf-in.
Conductor cross section AWG30 ... 12

UL connection data

Conductor cross section AWG16 ... 12
Tightening torque4.4 lbf-in.

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.