PHOENIX CONTACT PLT-SEC-T3-230-P-UT/PT PLT-SEC-T3-230-P-UT/PT 2907923 PHOENIX CONTACT Type 3 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLT-SEC-T3-230-P-UT/PT 2907923 PHOENIX CONTACT Type 3 surge protection plug

PLT-SEC-T3-230-P-UT/PT

2907923

PHOENIX CONTACT

1 Pcs.

Type 3 surge protection plug Replacement connector for type 2/3 surge protection from the PLT-SEC-...-UT/PT product series. Nominal voltage 230 V.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2907923
Packing unit10 pc
GTIN4055626257600
Weight per Piece (excluding packing)33.160 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.7 mm
Width17.5 mm
Depth65.7 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 ... 500 Hz / 2.5 h / X, Y, Z)

General

EN typeT2 / T3
IEC power supply systemTN-S
TT
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
Mounting typeon base element
Colorlight gray RAL 7035
Housing materialPA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions2
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs5 kA
Standby power consumption PC≤ 26.4 mVA (at UREF)
≤ 26.4 mVA (at UC)
Reference test voltage UREF264 V AC
Max. discharge current Imax(8/20) µs10 kA
Combination wave UOC6 kV
Voltage protection level Up(L-N)≤ 1.25 kV (at UOC)
≤ 1.4 kV (at In)
Voltage protection level Up(L-PE)≤ 1.4 kV
Voltage protection level Up(N-PE)≤ 1.4 kV
TOV behavior at UT(L-N)400 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
1464 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Short-circuit current rating ISCCR10 kA AC
Max. backup fuse with branch wiring32 A (gG / B / C)

Additional technical data

Short-circuit current rating ISCCR0.25 kA DC (without additional backup fuse)
5 kA DC (for 20 A gG / B backup fuse)
Maximum continuous voltage UC240 V DC
IEC test classification (in accordance with IEC 61643-21)D1
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Impulse durability (line-line)D1 - 500 A
Impulse durability (line-earth)D1 - 500 A
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV264 V AC
240 V DC
Nominal voltage240 V DC
Mode of protectionL-N
L-G
N-G
(DC+) - (DC-)
(DC+) - G
(DC-) - G
Power distribution systemSingle phase
DC
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1150 V
Measured limiting voltage MLV (L-G)1180 V
Measured limiting voltage MLV (N-G)1180 V
Nominal discharge current In5 kA

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.