PHOENIX CONTACT PLT-SEC-T3-230-FM-PT PLT-SEC-T3-230-FM-PT 2907928 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLT-SEC-T3-230-FM-PT 2907928 PHOENIX CONTACT Type 3 surge protection device

PLT-SEC-T3-230-FM-PT

2907928

PHOENIX CONTACT

1 Pcs.

Type 3 surge protection device Type 2/3 surge protection, consisting of a plug-in protection and a base element with push-in connection. For single-phase power supply networks with integrated status indication and remote signal. Rated Voltage: 230VAC/DC

Automation > Surge protection device for terminal equipment
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2907928
Packing unit5 pc
GTIN4055626257655
Weight per Piece (excluding packing)77.160 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height101 mm
Width17.7 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (operating voltage remote contact ≤ 250 V)
≤ 6000 m (operating voltage remote contact ≤ 150 V)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 ... 500 Hz / 2.5 h / X, Y, Z)

General

EN typeT2 / T3
IEC power supply systemTN-S
TT
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorlight gray RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL26 A (at 30 °C)
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs5 kA
Standby power consumption PC≤ 26.4 mVA (at UREF)
≤ 26.4 mVA (at UC)
Reference test voltage UREF264 V AC
Max. discharge current Imax(8/20) µs10 kA
Combination wave UOC6 kV
Voltage protection level Up(L-N)≤ 1.25 kV (at UOC)
≤ 1.4 kV (at In)
Voltage protection level Up(L-PE)≤ 1.4 kV
Voltage protection level Up(N-PE)≤ 1.4 kV
TOV behavior at UT(L-N)400 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
1464 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Short-circuit current rating ISCCR10 kA AC
Max. backup fuse with branch wiring32 A (gG / B / C)
Maximum backup fuse for through wiring25 A (gG / B / C)

Additional technical data

Short-circuit current rating ISCCR0.25 kA DC (without additional backup fuse)
5 kA DC (for 20 A gG / B backup fuse)
Maximum continuous voltage UC240 V DC
IEC test classification (in accordance with IEC 61643-21)D1
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Impulse durability (line-line)D1 - 500 A
Impulse durability (line-earth)D1 - 500 A
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA

Indicator/remote signaling

Switching functionPDT contact
Operating voltage250 V AC
125 V DC (200 mA DC)
Operating current0.5 A AC
0.5 A DC (75 V DC)
Connection methodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section AWG30 ... 12
Stripping length10 mm

Connection data

Connection methodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Stripping length10 mm

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


ETIM for 2907928 Earthing, lightning and surge protection (EC000942)
Feature Name Feature Value
Max. continuous voltage AC (EF004198) 264 V
Voltage protection level L-N (EF004236) 1.25 kV
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Max. conductor cross section solid (solid, stranded) (EF008827) 4 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 2.5 mm²
With remote signalling contact (EF000422) Yes
Signalling at the device (EF004241) Optic
Category type 3 (EF004231) No
Degree of protection (IP) (EF005474) IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.