PHOENIX CONTACT PTU 35/4X6/6X2,5 PTU 35/4X6/6X2,5 3214080 PHOENIX CONTACT Potential collective terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PTU 35/4X6/6X2,5 3214080 PHOENIX CONTACT Potential collective terminal

PTU 35/4X6/6X2,5

3214080

PHOENIX CONTACT

20 Pcs.

Potential collective terminal Collective potential terminal, nominal voltage: 1000 V, nominal current: 105 A, number of connections: 11, connection type: Screw connection, 1st floor, left-hand connection, cross-section: 1.5 mm² - 50 mm², Push-in connection, 1 inner floor connection, Dimensioning cross-section: 6 mm², cross-section: 0.5 mm² - 10 mm², mounting class: NS 35/7.5, NS 35/15, Color: Gray Potential collective terminal, In the end application, the applicable safety regulations for overload and short-circuit protection on the connected conductors must be considered., nom. voltage: 1000 V, nominal current: 105 A, 1st level connection left, connection method: Screw connection, cross section: 1.5 mm2 - 50 mm2, First level connection, interior, connection method: Push-in connection, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 10 mm2, mounting: NS 35/7,5, NS 35/15, color: gray

Automation > Feed-through terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
Notes on operationIn the end application, the applicable safety regulations for overload and short-circuit protection on the connected conductors must be considered.

Product properties
Product typePotential distributor
Number of connections11
Number of rows1
Potentials1
Data management status
Article revision06
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3

Electrical properties
Rated surge voltage8 kV
Maximum power dissipation for nominal condition4.06 W

Connection data
Service Entranceyes
Number of connections per level11
1st level connection left
Screw threadM6
Tightening torque3.2 ... 3.7 Nm
Stripping length18 mm
Internal cylindrical gageB9
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid1.5 mm² ... 50 mm²
Cross section AWG14 ... 2 (converted acc. to IEC)
Conductor cross section flexible1.5 mm² ... 50 mm²
Conductor cross section, flexible [AWG]14 ... 2 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)1.5 mm² ... 35 mm²
Flexible conductor cross section (ferrule with plastic sleeve)1.5 mm² ... 35 mm²
2 conductors with same cross section, solid1.5 mm² ... 16 mm²
2 conductors with the same cross-section AWG rigid16 ... 6 (converted acc. to IEC)
2 conductors with same cross section, flexible1.5 mm² ... 10 mm²
2 conductors with the same cross-section AWG flexible16 ... 8 (converted acc. to IEC)
2 conductors with same cross section, flexible, with ferrule without plastic sleeve1.5 mm² ... 10 mm²
Nominal current105 A
Maximum load current105 A (The maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal voltage1000 V
First level connection, interior
Stripping length12 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.5 mm² ... 10 mm²
Cross section AWG20 ... 8 (converted acc. to IEC)
Conductor cross section flexible0.5 mm² ... 6 mm²
Conductor cross section, flexible [AWG]20 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.5 mm² ... 10 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 10 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Nominal current41 A
Maximum load current41 A
Nominal voltage1000 V
Nominal cross section6 mm²
1st level connection right
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.14 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]26 ... 14 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 2.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Nominal current24 A
Maximum load current24 A
Nominal voltage1000 V
Nominal cross section2.5 mm²
First level connection, interior Connection cross sections directly pluggable
Conductor cross section rigid1 mm² ... 10 mm²
Conductor cross section, rigid [AWG]18 ... 8 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)1 mm² ... 6 mm²
Flexible conductor cross section (ferrule with plastic sleeve)1 mm² ... 6 mm²
1st level connection right Connection cross sections directly pluggable
Conductor cross section rigid0.34 mm² ... 4 mm²
Conductor cross-section flexible (ferrule without plastic sleeve)0.34 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.34 mm² ... 2.5 mm²

Dimensions
Width16.3 mm
Height110.4 mm
Depth on NS 35/7,548.8 mm
Depth on NS 35/1556.3 mm

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed

Electrical tests
Surge voltage test
Test voltage setpoint9.8 kV
ResultTest passed
Short-time withstand current 35 mm²3 kA
Short-time withstand current 50 mm²4.8 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint2.2 kV
ResultTest passed

Mechanical properties
Mechanical data
Open side panelNo

Mechanical tests
Mechanical strength
ResultTest passed
Attachment on the carrier
DIN rail/fixing supportNS 35
Test force setpoint10 N
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight1.5 mm² / 0.4 kg
35 mm² / 6.8 kg
50 mm² / 9.5 kg
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.5 mm² / 0.3 kg
6 mm² / 1.4 kg
10 mm² / 2 kg
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
ResultTest passed

Environmental and real-life conditions
Aging
Temperature cycles192
ResultTest passed
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 2, bogie-mounted
Frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %

Standards and regulations
Connection in acc. with standardIEC 60947-7-1
IEC 60947-7-1
IEC 60947-7-1

Mounting
Mounting typeNS 35/7,5
NS 35/15

ETIM for 3214080 Terminal blocks (EC000897)
Feature Name Feature Value
Rated current In (EF008250) 105 A
Rated voltage (EF000228) 1000 V
Type of electrical connection 1 (EF002526) Screw connection
Type of electrical connection 2 (EF002527) Screw connection
Number of levels (EF002659) 1
Number of clamp positions per level (EF002660) 11
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Material insulation body (EF007543) Other
Inflammability class of insulation material according to UL94 (EF002521) V0
Width (EF000008) 16.3 mm
Height (EF000040) 110.4 mm
Depth (EF000049) 48.8 mm
Closing plate required (EF002525) No
Colour (EF000007) Grey

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.