PHOENIX CONTACT PACT RCP-D190 PACT RCP-D190 2904892 PHOENIX CONTACT Coil View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PACT RCP-D190 2904892 PHOENIX CONTACT Coil

PACT RCP-D190

2904892

PHOENIX CONTACT

1 Pcs.

Coil Rogowski coil with a length of 600 mm. The diameter of the measuring coil in installed state is 190 mm. The Rogowski coil is used for the measurement of AC current from busbars and high-voltage lines.

Automation > Accessories/spare parts for low-voltage switch technology
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2904892
Packing unit1 pc
NoteMade to Order (non-returnable)
GTIN4046356898195
Weight per Piece (excluding packing)181.500 g
Custom tariff number90309000
Country of originIT (Italy)

Measuring coil input data

Frequency measuring range40 Hz ... 20000 Hz
Position error< 1 %
Linearity error0.1 %

Measuring coil signal output

Output signal (at 50 Hz)100 mV (no load, at 1,000 A)
Output voltage (in no-load operation)VOUT= M * dI/dt
Output voltage (sinusoidal, in no-load operation)100 mV (VOUT= 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))

General data, measuring coil

Length of measuring coil600 mm
Diameter of measuring coil8.3 mm ±0.2 mm
Length of signal cable3000 mm
Conductor structure signal line2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Coil materialElastollan
Housing materialPC
Insulationdouble insulation
Rated insulation voltage1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage10.45 kV (DC / 1 min.)
Basic accuracy
UL, USA/CanadaUL 61010 Recognized

General data

Standards/regulationsIEC 61010-1
IEC 61010-2-032

Standards and Regulations

Standards/regulationsIEC 61010-1
IEC 61010-2-032
UL, USA/CanadaUL 61010 Recognized

Ambient conditions

Ambient temperature (operation)-30 °C ... 80 °C (Measuring coil)
Ambient temperature (storage/transport)-40 °C ... 80 °C (Measuring coil)
Maximum altitude< 2000 m
Measuring coil degree of protectionIP67 (not assessed by UL)

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.