Hybrid motor starter Networkable hybrid start controller for starting 3~ AC motors up to 500 V AC, output current: 9 A, emergency stop function, adjustable overload disconnect and push-in connection, bus connector for attached rail.

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905143
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 26 (C-5-2017)
GTIN4046356920353
Weight per Piece (excluding packing)282.700 g
Custom tariff number85371098
Country of originDE (Germany)

Device supply

Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS60 mA
Type of protectionSurge protection
Reverse polarity protection

Input data

Input nameEnable input
NoteThe enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),
unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC7 mA
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms
Type of protectionReverse polarity protection

Output data load output

Output nameAC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie9 A (AC-51)
7 A (AC-53a)
Mains frequency50/60 Hz
Load current range1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Cooling time20 min. (for auto reset)
Leakage current0 mA
Type of protectionSurge protection

Overspeed tripping

Operate threshold> 60 A
Response time< 0.5 s

General

Switching frequency≤ 2 Hz (Load-dependent)
Mounting positionvertical (horizontal DIN rail, motor output below)
Mounting typeDIN rail mounting
Assembly instructionsalignable, for spacing see derating
Operating mode100% operating factor
Maximum power dissipation7 W
Minimum power dissipation0.88 W
Operating voltage displayGreen LED
Status displayYellow LED
IndicationRed LED

Connection data, input side

Connection nameControl circuits
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Connection data, output side

Connection nameLoad circuit
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Ambient conditions

Ambient temperature (operation)-5 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Degree of protectionIP20

Dimensions

Width22.5 mm
Height107.4 mm
Depth113.7 mm

UL data

SCCR100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA7.6 A (480 V AC)
Group installation20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category codeNLDX / NRNT
Horsepower ratings2 hp (120 V AC / 208 V AC)
5 hp (277 V AC / 480 V AC)

Insulation characteristics

Rated insulation voltage550 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
DesignationInsulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
InsulationSafe isolation (IEC 60947-1)
DesignationIsolation characteristics between the control input and control supply voltage to auxiliary circuit
InsulationSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC

Standards and Regulations

DesignationStandards/regulations
Standards/regulationsIEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
ATEX II (2) G [Ex e] [Ex d] [Ex px]
 II (2) D [Ex t] [Ex p]

Approvals/conformities

Safety Integrity Level according to IEC 61508≤ 3 (Safe shutdown)
2 (Motor protection)
Category acc. to EN ISO 13849≤ 3 (Safe shutdown)
Performance level according to ISO 13849e (Safe shutdown)
ATEX II (2) G [Ex e] [Ex d] [Ex px]
 II (2) D [Ex t] [Ex p]
EU-type examination certificatePTB 15 ATEX 3000
UL certificateNLDX.E228652
NRNT.E172140

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2905143 Low-voltage industrial controls and switchgear (EC001037)
Feature Name Feature Value
Type of motor starter (EF009598) Direct starter
With short-circuit release (EF006691) No
Rated control supply voltage DC (EF003980) 19.2 V
Voltage type for actuating (EF008242) DC
Rated operation current Ie (EF001443) 9 A
Rated operation current at AC-3, 400 V (EF009602) 9 A
Overload release current setting (EF002336) 1.5 A
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as normally closed contact (EF001377) 0
Temperature compensated overload protection (EF009604) No
Release class (EF006668) CLASS 10
Type of electrical connection of main circuit (EF006819) Spring clamp connection
Type of electrical connection for auxiliary- and control current circuit (EF006979) Spring clamp connection
Suitable for rail mounting (EF003972) Yes
Number of command positions (EF001372) 0
Suitable for emergency stop (EF001433) Yes
External reset possible (EF003426) Yes
Degree of protection (IP) (EF005474) IP20
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for Modbus (EF003057) No
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) Yes
Width (EF000008) 22.5 mm
Height (EF000040) 107.5 mm
Depth (EF000049) 114 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.