PHOENIX CONTACT NBC-M12MSD/0,15-93E/M12FSD 3X4 NBC-M12MSD/0,15-93E/M12FSD 3X4 1525905 PHOENIX CONTACT Network cable, PROFINET CAT5 (100 MBit/s), EtherCAT® .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NBC-M12MSD/0,15-93E/M12FSD 3X4 1525905 PHOENIX CONTACT Network cable, PROFINET CAT5 (100 MBit/s), EtherCAT® ..

NBC-M12MSD/0,15-93E/M12FSD 3X4

1525905

PHOENIX CONTACT

100 Pcs.

Network cable, PROFINET CAT5 (100 MBit/s), EtherCAT® CAT5 (100 MBit/s), 4-pole, halogen-free PUR, water blue RAL 5021, Straight connector M12, coding: D / IP67, a straight female M12, coding: D / IP67, cable length: 0.15 m Network cable, PROFINET CAT5 (100 MBit/s), EtherCAT® CAT5 (100 MBit/s), 4-pole, M12 straight connector, coding: D/IP67, a M12 straight female, encoding: D/IP67, cable length: 0.15 m Network cable, PROFINET CAT5 (100 Mbps), EtherCAT® CAT5 (100 Mbps), 4-position, Plug straight M12, coding: D / IP67, on Socket straight M12, coding: D / IP67, cable length: 0.15 m

Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
GeneralThis product corresponds to the PROFINET Cabling and Interconnection Technology Guideline for PROFINET regulations, version 2.00, order no: 2.252, Chapter 10.1 Cord Sets for Balanced Cabling
GeneralFurther products with variable cable type and variable cable length can be found in the accessories section

Product properties
Product typeData cable preassembled
Sensor typePROFINET
Number of positions4
ApplicationStandard
No. of cable outlets1
Shieldedyes
CodingD
Insulation characteristics
Overvoltage categoryII
Degree of pollution3

Interfaces
Bus systemPROFINET
Signal type/categoryPROFINET CAT5 (IEC 11801), 100 Mbps
EtherCAT®CAT5 (IEC 11801), 100 Mbps

Signaling
Status displayNo
Status display presentNo

Electrical properties
Nominal voltage UN48 V AC
60 V DC
Nominal current IN4 A
Transmission mediumCopper
Transmission characteristics (category)CAT5 (IEC 11801:2002)

Material specifications
Flammability rating according to UL 94V0

Connector
Connection 1
Ambient temperature (operation)-25 °C ... 90 °C
Connection 2
TypeSocket straight M12 / IP67
Number of positions4
Coding typeD (Data)
Handle colorblack
MaterialCuSn (Contact)
Ni/Au (Contact surface)
PA (Contact carriers)
TPU, hardly inflammable, self-extinguishing (Grip)
Zinc die-cast, nickel-plated (Screw connection)
FKM (Seal)
Insertion/withdrawal cycles≥ 100
Contact resistance≤ 5 mΩ
Insulation resistance≥ 100 MΩ
Tightening torque0.4 Nm
Degree of protectionIP67
Ambient temperature (operation)-25 °C ... 90 °C

Cable/line
Cable length0.15 m
Ethernet flexible CAT5, 2-pair [93E]
Dimensional drawinghmwurhgqiu.jpg
Shieldedyes
UL AWM Style20963 (80°C/30 V)
Cable weight42 kg/km
Cable typeEthernet flexible CAT5, 2-pair
Short symbol02YS(ST)C11Y
Cable type (abbreviation)93E
Signal type/categoryEthernet CAT5 (IEC 11801), 100 Mbps
Cable structure2x2xAWG26/7, SF/UTP
External cable diameter6.4 mm ±0.2 mm
Outer sheath, materialPUR
External sheath, colorwater blue RAL 5021
Thickness, outer sheath1.2 mm
Conductor materialBare Cu litz wires
Conductor structure signal line7x 0.16 mm
AWG signal line26
Conductor cross section2x 2x 0.14 mm²
Material wire insulationFoamed PE
Wire diameter incl. insulation0.98 mm
Single wire, colorwhite/orange-orange, white/green-green
Twisted pairs2 cores to the pair
Overall twistTwo pairs with two fillers to the core
ShieldingAluminum-coated foil, tinned copper braided shield
Optical shield covering70 %
Current carrying capacity of cable2 A (according to DIN VDE 0891-1)
Nominal voltage, cable≤ 100 V (Peak value, not for high-power applications)
Test voltage Core/Core700 V (50 Hz, 1 min.)
Test voltage Core/Shield700 V (50 Hz, 1 min.)
Cable insulation resistance≥ 500 MΩ*km
Coupling resistance≤ 100.00 mΩ/m (at 10 MHz)
Wave impedance100 Ω ±5 Ω (at 100 MHz)
Loop resistance≤ 290.00 Ω/km
Cable capacityapprox. 45 nF/km (at 1 kHz)
Signal runtime5.3 ns/m
Tensile strength≤ 80 N
Minimum bending radius, fixed installation4 x D
Minimum bending radius, flexible installation8 x D
Damping3.2 dB (with 1 MHz)
6 dB (at 4 МHz)
9.5 dB (at 10 MHz)
12.1 dB (at 16 MHz)
13.6 dB (at 20 МHz)
17.1 dB (at 31.25 МHz)
24.8 dB (at 62.5 МHz)
32 dB (at 100 MHz)
Near end crosstalk attenuation (NEXT)65.3 dB (with 1 MHz)
56.3 dB (at 4 МHz)
50.3 dB (at 10 MHz)
47.2 dB (at 16 MHz)
45.8 dB (at 20 МHz)
42.9 dB (at 31.25 МHz)
38.4 dB (at 62.5 МHz)
35.3 dB (at 100 MHz)
Power-summated near end crosstalk attenuation (PSNEXT)62.3 dB (with 1 MHz)
53.3 dB (at 4 МHz)
47.3 dB (at 10 MHz)
44.2 dB (at 16 MHz)
42.8 dB (at 20 МHz)
39.9 dB (at 31.25 МHz)
35.4 dB (at 62.5 МHz)
32.3 dB (at 100 MHz)
Return attenuation (RL)23 dB (at 4 МHz)
24.1 dB (at 8 МHz)
25 dB (at 10 MHz)
25 dB (at 16 MHz)
25 dB (at 20 МHz)
23.6 dB (at 31.25 МHz)
21.5 dB (at 62.5 МHz)
20.1 dB (at 100 MHz)
Halogen-freeaccording to IEC 60754-1
Resistance to oilin accordance with EN 60811-2-1
Flame resistanceaccording to IEC 60332-1-2
in acc. to UL VW1
in accordance with UN ECE-R 118.03
Ambient temperature (operation)-20 °C ... 80 °C (Cable, flexible installation)
-40 °C ... 80 °C (cable, fixed installation)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP65
IP67

Standards and regulations
M12
Standard designationM12 connector
Standards/specificationsIEC 61076-2-101

ETIM for 1525905 Sensors (EC001855)
Feature Name Feature Value
Number of poles (EF001391) 4
Type of electrical connection, field-sided (EF005525) M12
Type of plug-in contact, field sided (EF006269) Female (bus)
Positioning cable feed, field-sided (EF005928) Straight
Type of electrical connection, box-sided (EF005524) M12
Positioning cable feed, box-sided (EF005927) Straight
Cable length (EF000536) 0.15 m
Material of cable sheath (EF004136) Other
Halogen free (EF000025) No
Colour cable sheath (EF008249) Other
With LED indication (EF005950) No
Screened (EF000881) Yes
Vulcanize (EF004115) No
Material contact body (EF008248) Other
Permitted cable outer temperature after assembling without vibration (EF001686) -40 °C
Permitted cable outer temperature during assembling/handling (EF001685) -20 °C
Rated current In (EF008250) 4 A
Rated voltage (EF000228) 48 V
Degree of protection (IP) (EF005474) IP65

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.