View larger
PSR-SCP-24DC/MXF4/4X1/2X2/B
2903260
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2903260 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 266 (C-6-2017) |
| GTIN | 4046356729246 |
| Weight per Piece (excluding packing) | 99.990 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Ambient temperature (operation) | -20 °C ... 45 °C (see derating curve) |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Rated control circuit supply voltage US | |
|---|---|
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Typical input current at UN | 125 mA (with actuated relays) |
| 55 mA (Two-channel 24 V/0 V + max. 200 mA control (message outputs 32/62) with non-actuated relays) | |
| Current consumption | typ. 5 mA (Imax/Ixinputs) |
| 20 mA (in electric torque) | |
| Voltage at input/start and feedback circuit | 24 V -15 %; +10 % (first channel: 24 V; second channel: 0 V) |
| Typical response time | 175 ms (monitored/manual start) |
| 250 ms (automatic start) | |
| Typ. starting time with Us | 250 ms (when controlled via A1) |
| Typical release time | 25 ms (when controlled via S11/S12 and S21/S22) |
| 20 ms (when controlled via A1) | |
| Concurrence input 1/2 | ∞ |
| Recovery time | 1 s (Availability time after activation of sensor circuit: 100ms) |
| Operating voltage display | 1 x green LED |
| Status display | 5 green LEDs |
| Protective circuit | Surge protection Suppressor diode |
| Maximum switching frequency | 0.5 Hz |
| Max. permissible overall conductor resistance | 100 Ω |
| Filter time | max. 1.5 ms (Test pulse duration; for all equivalent inputs) |
| min. 7.5 ms (Test pulse rate; for all equivalent inputs) |
| Contact type | 4 enabling current paths |
|---|---|
| 2 semiconductor alarm outputs | |
| Contact material | AgCuNi, +0.2 -0.4 µm Au |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 10 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| max. 100 mA (Alarm output (24 V DC)) | |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2(ITH2= I12+ I22+ I32+ I42) |
| Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
| 66 W (220 V DC, τ = 0 ms) | |
| 66 W (110 V DC, τ = 0 ms) | |
| 100 W (48 V DC, τ = 0 ms) | |
| 144 W (24 V DC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
| 43 W (48 V DC, τ = 40 ms) | |
| Switching capacity min. | 0.1 W |
| Mechanical service life | 10x 106cycles |
| Switching capacity (360/h cycles) | 5 A (0,1 Hz; DC13; 24 V) |
| Output fuse | 6 A gL/gG NEOZED (N/O contact) |
| 4 A gL/gG NEOZED (for low-demand applications) |
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 99.99 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing color | yellow |
| Connection method | Screw connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Stop category | 0 |
|---|---|
| Safety Integrity Level (SIL) | 3 |
| 3 | |
| Designation | EN ISO 13849 |
| Performance level (PL) | e (5 A DC13; 3 A AC15; 8760 cycles/year) |
| Category | 4 |
| Safety Integrity Level Claim Limit (SIL CL) | 3 |
| Designation | EN 50156 |
| Safety Integrity Level (SIL) | 3 |
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178/VDE 0160 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | 4 kV/basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit, enabling current paths and safety circuit 1 (13/14, 23/24) and safety circuit 2 (43/44, 53/54).) |
| Degree of pollution | 2 |
| Overvoltage category | III |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |