PHOENIX CONTACT MT-RS485 MT-RS485 2762265 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MT-RS485 2762265 PHOENIX CONTACT Surge protection device

MT-RS485

2762265

PHOENIX CONTACT

1 Pcs.

Surge protection device Rail mounting module with coarse and fine surge protection for RS-485 interface, for mounting on NS 35/7.5, housing width: 50 mm

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2762265
Packing unit5 pc
Catalog pagePage 100 (TT-2002)
GTIN4017918064945
Weight per Piece (excluding packing)101.950 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height77.5 mm
Width47.6 mm
Depth54.9 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 60 °C
Degree of protectionIP20

General

Colorblack
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece
Direction of actionLine-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationC2
C3
D1
VDE requirement classC2
C3
D1
Maximum continuous voltage UC12 V DC
Rated current450 mA (25 °C)
Operating effective current ICat UC≤ 10 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs500 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 22 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 600 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 22 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 600 V
Output voltage limitation at 1 kV/µs (line-signalground) static≤ 22 V
Residual voltage at In(line-line)≤ 19 V
Residual voltage at In(line-signalground)≤ 19 V
Voltage protection level Up(line-line)≤ 22 V
Voltage protection level Up(line-earth)≤ 600 V
Voltage protection level Up(line-signalground)≤ 22 V
Response time tA(line-line)1 ns
Response time tA (line-signalground)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.
≤ 0.1 dB (up to 10 kHz)
Input attenuation aE, asym.0.8 dB (up to 0.1 MHz 50 Ω system)
0.1 dB (up to 10 kHz 600 Ω system)
Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system1.3 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 600 Ohm system130 kHz
Resistance in series4.4 Ω
Surge protection fault messagenone

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.