PHOENIX CONTACT HDFK 50-VP/Z IB/WS HDFK 50-VP/Z IB/WS 1711258 PHOENIX CONTACT Panel feed-through terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

HDFK 50-VP/Z IB/WS 1711258 PHOENIX CONTACT Panel feed-through terminal block

HDFK 50-VP/Z IB/WS

1711258

PHOENIX CONTACT

10 Pcs.

Panel feed-through terminal block Terminal block, connection type: Screw connection with traction capsule, Terminal connection, number of poles: 1, charging current: 150 A, cross-section: 16 mm² - 50 mm², conductor connection direction with respect to the plug direction: 0 °, width: 18.8 mm Panel feed-through terminal block, connection method: Screw connection with tension sleeve, Cable lug connection, number of positions: 1, load current: 150 A, cross section: 16 mm2 - 50 mm2, connection direction of the conductor to plug-in direction: 0 °, width: 18.8 mm, color: gray

Automation > Panel feed-through terminal block
PCB Connectors (PCC)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typePanel feed-through terminal block
Product familyHDFK 50-VP
Number of positions1
Pitch18.8 mm
Data management status
Article revision02

Electrical properties
Nominal current IN150 A
Nominal voltage UN690 V
Rated voltage (III/3)690 V
Rated surge voltage (III/3)8 kV

Connection data
Connection technology
Connector systemHDFK 50
Nominal cross section50 mm²
Conductor connection exterior
Connection methodScrew connection with tension sleeve
Connection direction of the conductor to plug-in direction0 °
Conductor cross section rigid16 mm² ... 50 mm²
Conductor cross section flexible16 mm² ... 50 mm²
Conductor cross section flexible, with ferrule without plastic sleeve10 mm² ... 50 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve10 mm² ... 50 mm²
2 conductors with same cross section, solid6 mm² ... 16 mm²
2 conductors with same cross section, flexible10 mm² ... 16 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve6 mm² ... 16 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve6 mm² ... 10 mm²
Internal cylindrical gageB10
Stripping length24 mm
Tightening torque6 Nm ... 8 Nm
Conductor connection interior
Connection methodCable lug connection
Connection direction of the conductor to plug-in direction0 °

Material specifications
Material data - contact
NoteWEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201
Contact materialCu alloy
Surface characteristicstin-plated
Material data - housing
Color (Housing)gray (7042)
Insulating materialPA
Insulating material groupI
CTI according to IEC 60112600
Flammability rating according to UL 94V0
Glow wire flammability index GWFI according to EN 60695-2-12850
Glow wire ignition temperature GWIT according to EN 60695-2-13775
Temperature for the ball pressure test according to EN 60695-10-2125 °C

Notes
Safety note
Safety note• Only electrically qualified personnel may install and operate the product.
To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering.
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data.
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection.
• To maintain the nominal voltage, align the cable lugs straight and centered, and cast the terminals on the inside.
 There is no electrical contact to the housing. Make sure that protective grounding is provided for green/yellow color variants and articles marked with PE.

Dimensions
Dimensional drawingddiurgchyv.jpg
Pitch18.8 mm
Width [w]18.8 mm
External dimensions
Height [h3]54 mm
Length [l1]43 mm
Internal dimensions
Height [h4]37 mm
Length [l2]35 mm

Electrical tests
Air clearances and creepage distances 1. Insulation coordination
ApplicationMetal wall 4.5 mm ... 6.0 mm
Internal part molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)690 V
Rated surge voltage (III/3)8 kV
minimum clearance value - non-homogenous field (III/3)8 mm
minimum creepage distance (III/3)8 mm
Air clearances and creepage distances 2. Insulation coordination
ApplicationMetal panel 2.0 mm ... 4.5 mm
Internal part molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)800 V
Rated surge voltage (III/3)8 kV
minimum clearance value - non-homogenous field (III/3)8 mm
minimum creepage distance (III/3)10 mm
Air clearances and creepage distances 3. Insulation coordination
ApplicationMetal panel 1.0 mm ... 2.0 mm
Internal part molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)1000 V
Rated surge voltage (III/3)8 kV
minimum clearance value - non-homogenous field (III/3)8 mm
minimum creepage distance (III/3)12.5 mm
Air clearances and creepage distances 4. Insulation coordination
ApplicationPlastic panel 1.0 ... 6.0 mm
Internal part molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)1000 V
Rated surge voltage (III/3)8 kV
minimum clearance value - non-homogenous field (III/3)8 mm
minimum creepage distance (III/3)12.5 mm
Air clearances and creepage distances 5. Insulation coordination
ApplicationMetal wall 1.0 mm ... 6.0 mm
Internal part not molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)250 V
Rated surge voltage (III/3)4 kV
minimum clearance value - non-homogenous field (III/3)3 mm
minimum creepage distance (III/3)3.2 mm
Air clearances and creepage distances 6. Insulation coordination
ApplicationPlastic panel 1.0 ... 6.0 mm
Internal part not molded
SpecificationIEC 60947-7-1:2002-07
Insulating material groupI
Comparative tracking index (IEC 60112)CTI 600
Rated insulation voltage (III/3)250 V
Rated surge voltage (III/3)4 kV
minimum clearance value - non-homogenous field (III/3)3 mm
minimum creepage distance (III/3)3.2 mm

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-40 °C ... 100 °C (Depending on the current carrying capacity/derating curve)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Relative humidity (storage/transport)30 % ... 70 %
Ambient temperature (assembly)-5 °C ... 100 °C

Packaging specifications
Type of packagingpacked in cardboard

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.