PHOENIX CONTACT PLC-APT-UI-IN PLC-APT-UI-IN 2906917 PHOENIX CONTACT Extension module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLC-APT-UI-IN 2906917 PHOENIX CONTACT Extension module

PLC-APT-UI-IN

2906917

PHOENIX CONTACT

1 Pcs.

Extension module Analog input module for PLC logic modules (generation 2 only), single-channel, signal type (4 ... 20 mA, 0 ... 20 mA, 0 ... 10 V, 2 ... 10 V) configurable via DIP switch, push-in connection

Automation > PLC analogue I/O-module
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2906917
Packing unit1 pc
Catalog pagePage 430 (C-5-2017)
GTIN4055626153780
Weight per Piece (excluding packing)53.300 g
Custom tariff number85389099
Country of originDE (Germany)

Dimensions

Width6.2 mm
Height80 mm
Depth86 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 50 °C
Ambient temperature (storage/transport)-20 °C ... 70 °C

Supply

Rated control circuit supply voltage US24 V DC
Rated control supply voltage range with reference to US0.8 ... 1.1
Rated control supply current IS13 mA
Type of protectionReverse polarity protection
Surge protection
Operating voltage displayGreen LED
IndicationRed LED

Input data

Input nameAnalog current input
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Input resistance current input~ 40 Ω
Maximum temperature coefficient0.01 %/K
Maximum transmission error1 %
Surge voltage protection> 33 V
Input nameAnalog voltage input
Voltage input signal0 V ... 10 V
2 V ... 10 V
Input resistance of voltage input> 120 kΩ
Maximum temperature coefficient0.01 %/K
Maximum transmission error1 %
Surge voltage protection> 33 V

Output data

Output nameDigital output

General

Operating mode100% operating factor
Degree of protectionIP20
Mounting positionany
Assembly instructionsIn rows with zero spacing

Connection data

Connection methodPush-in connection
Stripping length8 mm
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 14
Number of connections4

Standards and Regulations

DesignationAir clearances and creepage distances
Standards/regulationsDIN EN 50178
Rated insulation voltage50 V
Rated surge voltage0.5 kV
InsulationBasic insulation
Degree of pollution2
Overvoltage categoryIII
ConformanceCE-compliant
UL, USA/CanadaUL 508 Listed

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2906917 PLC's (EC001420)
Feature Name Feature Value
Number of analogue inputs (EF001994) 1
Number of analogue outputs (EF001995) 0
Analogue inputs configurable (EF008518) Yes
Analogue outputs configurable (EF008519) No
Input, current (EF003204) Yes
Input, voltage (EF003205) Yes
Input, resistor (EF003206) No
Input, resistance thermometer (EF003207) No
Input, thermocouple (EF003208) No
Input signal, configurable (EF003209) Yes
Resolution of the analogue inputs (EF003575) 10 Bit
Output, current (EF003212) No
Output, voltage (EF003213) No
Output signal configurable (EF003214) No
Type of electric connection (EF003961) Other
Suitable for safety functions (EF001597) No
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Width (EF000008) 6.2 mm
Height (EF000040) 80 mm
Depth (EF000049) 94 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.