PHOENIX CONTACT MINI MCR-EX-SD-21-48-LP-PT MINI MCR-EX-SD-21-48-LP-PT 2908811 PHOENIX CONTACT Ex i, Valve control block for operating intrinsically saf.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-EX-SD-21-48-LP-PT 2908811 PHOENIX CONTACT Ex i, Valve control block for operating intrinsically saf..

MINI MCR-EX-SD-21-48-LP-PT

2908811

PHOENIX CONTACT

1 Pcs.

Ex i, Valve control block for operating intrinsically safe solenoid valves in the zone Ex. No-load voltage: 21 V, current limiting: 48 mA, Loop-powered, Safety Integrity Level (SIL, IEC61508): 3, Push-in connection Ex i-Solenoid driver for controlling Ex i solenoid valves in the Ex area. no-load voltage: 21 V DC, current limitation: 48 mA, Standard configuration, Loop-powered, Safety Integrity Level (SIL, IEC 61508): 3, Push-in connection

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSolenoid driver
Product familyMINI Analog Pro

Electrical properties
Electrical isolation
Overvoltage categoryII (≤ 5000 m)
Pollution degree2 (≤ 5000 m)
Electrical isolation Input/output IEC/EN 61010-1
Standards/regulationsIEC/EN 61010-1
Rated insulation voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationDouble/reinforced insulation
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage265 Vrms
Electrical isolation Input/output IEC/EN 60079-7
Standards/regulationsIEC/EN 60079-7
Rated insulation voltage251 Vrms
Supply
Supply voltage rangeloop-powered, no external supply necessary
Power consumption< 1.7 W

Input data
Signal: Voltage
Number of inputs1
Voltage input signal19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)

Output data
Signal: Voltage
Number of outputs1
Output voltage≥ 12.2 V DC (48 mA)
Output resistor≥ 181 Ω (Internal resistance Ri)
Current limitation> 48 mA
Response time< 50 ms
Non-load voltage> 21 V DC
Short-circuit-proofyes

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12 (flexible)

Ex data
Ex installation (EPL)Gc
Div. 2
Ex i circuits (EPL)Ga
Da
Ma
Div. 1
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Ci11 nF
Max. output voltage Uo25.1 V
Max. output current Io139 mA
Max. output power Po872 mW
Safety-related maximum voltage Um253 V AC
125 V DC
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co10 mH / 2.92 µF
IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co5 mH / 819 nF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co1.5 mH / 97 nF
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co15 mH / 4.84 µF

Dimensions
Width6.2 mm
Height109.81 mm
Depth119.2 mm

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Altitude range (IEC/EN 61010-1)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage150 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 60079-11)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Safety-related maximum voltage Um121 V AC
110 V DC
Rated insulation voltage150 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage162 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage60 Vrms(Input/output)

Approvals
CE
CertificateCE-compliant
ATEX
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 ATEX 8651 X
IECEx
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
CertificateIECEx TUR 21.0043 X
UKCA Ex (UKEX)
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 UKEX 7021 X
CCC / China-Ex
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
Certificate2023122310116238
UL, USA/Canada
IdentificationUL 61010-2-201
Safety Integrity Level (SIL, IEC 61508)
Identification3

EMC data
Noise immunityIEC/EN 61000-6-2
IEC/EN 61326-3-2
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Noise emissionIEC/EN 61000-6-4

Standards and regulations
GB Standard
Standards/regulationsGB/T 3836.1
GB/T 3836.3
GB/T 3836.4

Mounting
Mounting typeDIN rail mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.