View larger
MINI MCR-SL-PT100-UI-NC
2864273
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2864273 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 105 (C-7-2015) |
| GTIN | 4017918956561 |
| Weight per Piece (excluding packing) | 99.200 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Configurable/programmable | Yes |
|---|---|
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
| Sensor input current | 1 mA (constant) |
| Connection technology | 2, 3, 4-wire |
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage output signal | 0 V ... 10 V |
| 10 V ... 0 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Max. output voltage | approx. 12.5 V |
| Max. output current | 23 mA |
| Short-circuit current | approx. 10 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | < 500 Ω (at 20 mA) |
| Ripple | < 20 mVPP(at 10 kΩ) |
| < 20 mVPP(at 500 Ω) |
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Max. current consumption | < 21 mA (at 24 V DC) |
| Power consumption | < 500 mW |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
| No. of channels | 1 |
|---|---|
| Transmission error in the set measuring range | ((100 K / set measurement range [K]) + 0.1)% |
| Transmission error in the full measuring range | ≤ 0,2 % |
| Maximum temperature coefficient | < 0.02 %/K |
| Protective circuit | Transient protection |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 50 V AC/DC |
| Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| GL | GL EMC 2 D |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 10 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 10 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 10 % |
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Basic insulation according to EN 61010 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| GL | GL EMC 2 D |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Measuring range (EF001836) | -150 °C |
| Analogue output 0 mA ... 20 mA (EF006808) | No |
| Analogue output 4 mA ... 20 mA (EF006810) | No |
| Analogue output 0 V ... 2 V (EF009886) | No |
| Analogue output 0 V ... 5 V (EF009887) | Yes |
| Analogue output 0 V ... 10 V (EF006807) | Yes |
| Analogue output 2 V ... 10 V (EF009888) | No |
| With switching output (EF005225) | No |
| Modular version (EF001126) | Yes |
| Integrated configuration function (EF003064) | Yes |
| EMC-version (EF001062) | Yes |
| Ambient temperature (EF002386) | 65 °C |
| Weight (EF000167) | 0.0977 kg |