PHOENIX CONTACT MINI MCR-SL-PT100-UI-200-NC MINI MCR-SL-PT100-UI-200-NC 2864370 PHOENIX CONTACT Temperature measuring transducer View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-SL-PT100-UI-200-NC 2864370 PHOENIX CONTACT Temperature measuring transducer

MINI MCR-SL-PT100-UI-200-NC

2864370

PHOENIX CONTACT

1 Pcs.

Temperature measuring transducer MCR temperature converter, configurable, for Pt 100 temperature sensors, screw connection, not configured MCR temperature transducer, configurable, for Pt 100 temperature sensors, with screw-connection, not configured

Automation > Temperature transformer
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
Utilization restriction
EMC noteEMC: class A product, see manufacturer's declaration in the download area

Product properties
Product typeTemperature transmitter
Product familyMINI Analog
ConfigurationDIP switches
Data management status
Article revision12
Insulation characteristics
Overvoltage categoryII
Pollution degree2

Electrical properties
Maximum power dissipation for nominal condition235.5 mW
Protective circuitTransient protection
Step response (0–99%)< 200 ms
Maximum temperature coefficient< 0.02 %/K
Transmission error in the set measuring range((50 K / Δ Temp)+ 0.05)%
Transmission error in the full measuring range≤ 0.25 %
Electrical isolation Input/output/power supply
Rated insulation voltage50 V AC/DC
Test voltage1.5 kV AC (50 Hz, 60 s)
InsulationBasic insulation in accordance with IEC/EN 61010
Supply
Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption< 21 mA (at 24 V DC)
Power consumption< 500 mW

Input data
Signal
Number of inputs1
Measurement
Sensor types (RTD) that can be usedPt 100 (IEC 60751/EN 60751)
Temperature measuring rangemin. 50 K
Sensor type:-50 °C ... 200 °C (configurable)
Sensor input current1 mA (constant)
Max. permissible overall conductor resistance10 Ω (Per cable)
Connection technology2-, 3-, 4-conductor

Output data
Signal: Voltage/current
Number of outputs1
Configurable/programmableYes
Voltage output signal0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal 12.5 V
Non-load voltage 12.5 V
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal23 mA
Short-circuit current 10 mA
Load/output load voltage output> 10 kΩ
Load/output load current output< 500 Ω (at 20 mA)
Ripple< 20 mVPP(at 500 Ω)
< 20 mVPP(at 10 kΩ)

Connection data
Connection methodScrew connection
Stripping length12 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 12

Dimensions
Dimensional drawingsmswzljhgb.jpg
Width6.2 mm
Height93.1 mm
Depth101.2 mm

Material specifications
Colorgreen (RAL 6021)
Housing materialPBT
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)

Approvals
CE
CertificateCE-compliant
UKCA
CertificateUKCA-compliant
UL, USA/Canada
IdentificationUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding approval
CertificateDNV GL TAA00002R0
DNV GL data
TemperatureB
HumidityB
VibrationB
EMCA
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data
Electromagnetic compatibilityConformance with EMC directive
Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Noise emissionEN 61000-6-4
Electrostatic discharge
Standards/regulationsEN 61000-4-2
Electrostatic discharge
CommentsSafety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value10 %
Fast transients (burst)
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value10 %
Surge current load (surge)
Standards/regulationsEN 61000-4-5
Surge current load (surge)
CommentsCriterion B
Conducted interference
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value10 %

Mounting
Mounting typeDIN rail mounting
Mounting positionany

ETIM for 2864370 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -50 °C
Analogue output 0 mA ... 20 mA (EF006808) No
Analogue output 4 mA ... 20 mA (EF006810) No
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) Yes
Analogue output 0 V ... 10 V (EF006807) Yes
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) No
Modular version (EF001126) Yes
Integrated configuration function (EF003064) Yes
EMC-version (EF001062) Yes
Ambient temperature (EF002386) 65 °C
Weight (EF000167) 0.05857 kg

Product Datasheet