PHOENIX CONTACT TTC-6-MOV-C-48DC-UT-I TTC-6-MOV-C-48DC-UT-I 2906838 PHOENIX CONTACT Medium surge protection with integrated status indicator for a.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6-MOV-C-48DC-UT-I 2906838 PHOENIX CONTACT Medium surge protection with integrated status indicator for a..

TTC-6-MOV-C-48DC-UT-I

2906838

PHOENIX CONTACT

1 Pcs.

Medium surge protection with integrated status indicator for a signal wire with grounded reference potential. Medium surge protection with integrated status indicator for one signal wire with grounded reference potential. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
TypeDIN rail module, one-piece
Surge protection fault messageoptical
Data management status
Article revision08
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN48 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawingdxsjqyksqp.jpg
Width6.2 mm
Height92 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelYes

Protective circuit
Direction of actionLine-Earth Ground
Maximum continuous voltage UC60 V DC
42 V AC
Rated current10 A (60 °C)
Operating effective current ICat UC≤ 100 µA
Residual current IPE≤ 100 µA
Nominal discharge current In(8/20) µs (line-ground)2 kA
Voltage protection level Up(line-earth)≤ 200 V (C1 - 600 A)
≤ 220 V (C2 - 4 kV)
≤ 150 V (C3 - 25 A)
≤ 160 V (C3 - 35 A)
Response time tA(line-earth)≤ 25 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 650 kHz
Capacity (Core-Earth)5 nF
Resistance per path≤ 100 mΩ
Surge protection fault messageoptical
Impulse durability (line-earth)C1 - 600 A
C2 - 2 kA
C3 - 35 A

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (with end cover)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: 35 mm

ETIM for 2906838 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 48 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.