PHOENIX CONTACT MACX MCR-EX-AP-2T-2I MACX MCR-EX-AP-2T-2I 1290780 PHOENIX CONTACT Ex i-Temperature converters, Ex i input signals of thermoresist.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MACX MCR-EX-AP-2T-2I 1290780 PHOENIX CONTACT Ex i-Temperature converters, Ex i input signals of thermoresist..

MACX MCR-EX-AP-2T-2I

1290780

PHOENIX CONTACT

1 Pcs.

Ex i-Temperature converters, Ex i input signals of thermoresistors in 2, 3 or 4 conductor technology, thermocouples and mV sources are converted into non-Ex i signals of 0 mA / 4 mA ... 20 mA active. Standard configuration, 5-way separation, Screw connection Ex i, Temperature converters, Ex i input signals of resistance thermometers in 2, 3 or 4 conductor technology, thermocouples and mV sources are converted to 0 mA / 4 mA non-Ex i signals... 20 mA active. 2 Channels, Universal, Free Programming, 5-Way Spacing, Screw Connection Ex i-Temperature transducer, input signals from resistance thermometers in 2, 3, or 4-conductor technology, thermocouples, and mV sources are converted into active 0 mA / 4 mA ... 20  mA non Ex i signals. Standard configuration, 5-way isolation, Screw connection

Automation > Temperature transformer
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
GeneralAccuracy, typically specified as a percentage of the basic measuring range at UN, 23°C
GeneralInstallation conditions influence the ambient temperature.
Please refer to the operating instructions.
GeneralOutput behavior = 2.4 mA (0 mA ... 23 mA or “Hold last value” can be configured)
GeneralSensor set via software or DIP switches
General2-conductor comparison set via DIP switch ADJ
GeneralThe input variables can be set via the ISpac Wizard parameterization software or DIP switches.

Product properties
Product typeTemperature transmitter
Product familyMACX Analog
No. of channels2
ConfigurationSoftware

Electrical properties
No. of channels2
Electrical isolation5-way isolation
Temperature coefficient, typical≤ 0.1 % (10 K)
Reverse polarity protectionyes
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/error message output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/configuration interface IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Output 1/output 2
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/supply
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/configuration interface
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/supply/error message output
Test voltage350 V (50 Hz, 60 s)
Supply
Nominal supply voltage24 V DC
Supply voltage range18 V ... 31.2 V
Power dissipation≤ 1.9 W
Power consumption≤ 1.9 W

Input data
Measurement
Description of the inputResistance temperature detector
Sensor types (RTD) that can be usedPt 100, Pt 250, Pt 500, Pt 1000, Pt 2000, Ni 100, Ni 500, Ni 1000, M50, M53, M100
Temperature measuring range-200 °C ... 1100 °C (Range depending on the sensor type)
Connection technology2-, 3-, 4-conductor
Max. permissible overall conductor resistance50 Ω (per wire, 2-conductor circuit)
100 Ω (per wire, 3-, 4-conductor circuit)
Temperature measuring range≥ 51 K (Range depending on the sensor type)
Measurement
Description of the inputThermocouple
Sensor types that can be used (TC)B, E, J, K, N, R, S, T, L, U, XK
Temperature measuring range-200 °C ... 1800 °C (Range depending on the sensor type)
Max. permissible overall conductor resistance≤ 1000 Ω (per wire)
Temperature measuring range≥ 36 K (Range depending on the sensor type)
Measurement
Description of the inputPotentiometer
Connection technology3-conductor
Linear resistance measuring range50 Ω ... 500 Ω
0.5 kΩ ... 5 kΩ
1 kΩ ... 10 kΩ
10 kΩ ... 100 kΩ (with parallel 10 kΩ shunt, no wire-break monitoring)

Output data
Signal: Error message output
Maximum switching voltage30 V
Max. switching current100 mA
Signal: Current
Current output signal0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
0 mA ... 21 mA (Function area)
Load0 Ω ... 600 Ω (per channel)

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Ex data
Ex installation (EPL)Gc
Ex i circuits (EPL)Ga
Da
Ma
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Cinegligible
Max. output voltage Uo6.5 V
Max. output current Io19.7 mA
Max. output power Po32 mW (linear characteristic curve)
Safety-related maximum voltage Um253 V AC
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co700 mH / 1000 µF
IIB (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co330 mH / 570 µF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co90 mH / 25 µF
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co700 mH / 1000 µF

Signaling
Status displayGreen LED (supply voltage)
Red LED (line errors)

Dimensions
Dimensional drawingkrbhdfxwui.jpg
Width17.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications
Flammability rating according to UL 94V0
Housing materialPolyamide (PA 6.6)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (Terminal blocks)
IP30 (Housing)
Ambient temperature (operation)-20 °C ... 70 °C (Stand-alone device: any mounting position)
-20 °C ... 40 °C (Group assembly: vertical DIN rail without circulating air)
-20 °C ... 60 °C (Group assembly: vertical DIN rail with circulating air)
-20 °C ... 50 °C (Group assembly: horizontal DIN rail without circulating air)
-20 °C ... 70 °C (Group assembly: horizontal DIN rail with circulating air)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Permissible humidity (operation)≤ 95 % (non-condensing)

Approvals
ATEX
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
IECEx
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA nC [ia Ga] IIC T4 Gc
[Ex ia Ma] I

EMC data
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21

Standards and regulations
Electrical isolation5-way isolation

Mounting
Mounting typeNS 35/15, NS 35/7,5
Mounting positionvertical, horizontal

ETIM for 1290780 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -200 °C
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) No
Analogue output 0 V ... 10 V (EF006807) No
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) No
Ambient temperature (EF002386) 70 °C
Weight (EF000167) 0.2286 kg

Product Datasheet