PHOENIX CONTACT MACX MCR-EX-AP-2REL-2DI-LP MACX MCR-EX-AP-2REL-2DI-LP 1292331 PHOENIX CONTACT The relay module separates the Ex i and non-Ex i control .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MACX MCR-EX-AP-2REL-2DI-LP 1292331 PHOENIX CONTACT The relay module separates the Ex i and non-Ex i control ..

MACX MCR-EX-AP-2REL-2DI-LP

1292331

PHOENIX CONTACT

1 Pcs.

The relay module separates the Ex i and non-Ex i control and signal circuits and serves for intrinsically safe control of Ex i field current circuits via one inverter relay per channel. Standard configuration, Loop-powered, 4-way separation, Safety Integrity Level (SIL, IEC 61508): 2, Screw connection

Automation > Accessories/spare parts for low-voltage switch technology
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
GeneralThe installation conditions influence the ambient temperature.
Please note the operating instructions.

Item Properties
Product TypeRelay module
Product FamilyMACX Analog
Number of channels2

Electrical Properties
Number of channels2
Galvanic Separation4-Way Separation
Galvanic Separation Input/Output IEC/EN 60079-11
Standards/SpecificationsIEC/EN 60079-11
Sizing Insulation Voltage375 VPP
Galvanic Separation Input 1 / Input 2
Test voltage350 V (50 Hz, 60 sec)
Feeding
Supply voltageLoop-powered, no external power required
Dissipated Power≤ 0.4 W

Input data
Control
Ticket DescriptionControl input, not intrinsically safe
Input Signal Voltage12 V ... 31.2 V (Switching Signal)
Current absorption< 25 mA (12 V)
< 17 mA (24 V ... 31.2 V)

Output Data
Commuting: Relay
Description of the outputIntrinsic safety
Contact Switching Type1 switched contact per channel
Minimum Activation Voltage1 V (1 mA)
Maximum Switching Voltage45 V DC (0.25 A)
30 V DC (4 A)
45 V AC (4 A, cos φ >0.7)
Typical Connection Time≤ 10 ms
Typical Shutdown Time≤ 10 ms
Switching frequency≤ 15 Hz

Connection data
AWG Conductor Section(Converted according to IEC)
Connection typeScrew connection
Length to be de-insulated7 mm
Screw threadM3
Rigid conductor section0.2 mm² ... 2.5 mm²
Flexible conductor section0.2 mm² ... 2.5 mm²
AWG Conductor Section24 ... 14

Ex Data
Ex Installation (EPL)Gc
Intrinsically safe circuits (EPL)Ga
Gives
Ma
Technical Safety Data
Input voltage Ui45 V AC
Input Current Ii4 A
Internal inductance max. Lidespicable
Max. Internal Capacity Cidespicable
Maximum safety voltage Um253 V AC
Technical Safety Data
Input voltage Ui45 V DC
Input Current Ii0.25 A
Internal inductance max. Lidespicable
Max. Internal Capacity Cidespicable
Maximum safety voltage Um253 V AC
Technical Safety Data
Input voltage Ui30 V DC
Input Current Ii4 A
Internal inductance max. Lidespicable
Max. Internal Capacity Cidespicable
Maximum safety voltage Um253 V AC

Dimensions
Dimension Schemekrbhdfxwui.jpg
Width17.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7.5114.5 mm (fitted on DIN rail NS 35/7.5 according to EN 60715)

Material Data
Flammability class according to UL 94V0
Shell materialPolyamide (PA 6.6)

Environmental and life-life conditions
Environmental conditions
Protection IndexIP20 (Terminals)
IP30 (Housing)
Ambient Temperature (Service)-20 °C ... 70 °C (Individual Equipment: Discretionary Mounting Position)
-20 °C ... 70 °C (Mounting in groups: vertical DIN rail without air circulation)
-20 °C ... 70 °C (Mounting in groups: vertical DIN rail with air circulation)
-20 °C ... 70 °C (Bracket mounting: horizontal DIN rail without air circulation)
-20 °C ... 70 °C (Bracket mounting: horizontal DIN rail with air circulation)
Ambient Temperature (Storage/Transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Permissible air humidity (service)≤ 95% (non-condensing)

Approvals
ATEX
Marked II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex ec nC [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
IECEx
Marked[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec nC [ia Ga] IIC T4 Gc
[Ex ia Ma] I
Safety Integrity Level (SIL, IEC 61508)
Marked2

EMC data
Electromagnetic compatibilityTesting according to the following standards and requirements: EN 61326-1 for use in the industrial field, NAMUR NE 21

Standards & Specifications
Galvanic Separation4-Way Separation

assembly
Type of mountingNS 35/15, NS 35/7.5
Position for mountingvertical, horizontal