PHOENIX CONTACT CTM 2X1-180DC-GS-P CTM 2X1-180DC-GS-P 2838623 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CTM 2X1-180DC-GS-P 2838623 PHOENIX CONTACT Surge protection plug

CTM 2X1-180DC-GS-P

2838623

PHOENIX CONTACT

1 Pcs.

Surge protection plug LSA-PLUS (COMTRAB CTM) plug-in protection with Powercross protection and sufficient surge protection for 2 signal conductors. Rated voltage: 180 V DC

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2838623
Packing unit10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 167 (C-4-2017)
GTIN4017918948375
Weight per Piece (excluding packing)8.340 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height21 mm
Width9.5 mm
Depth53.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
Overvoltage categoryII
Degree of pollution2
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Direction of actionLine-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 2.20
Near-end crosstalk attenuation aN between adjacent articles70 dB (up to 1 MHz 100 Ω system)
50 dB (up to 10 MHz 100 Ω system)
30 dB (up to 100 MHz, 100 Ω system)

Protective circuit

IEC test classificationA2
B1
B2
B3
C1
C2
C3
D1
D2
VDE requirement classA2
B1
B2
B3
C1
C2
C3
D1
D2
Nominal voltage UN180 V DC
Maximum continuous voltage UC± 180 V DC
Rated current120 mA (25 °C)
Operating effective current ICat UC≤ 2 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Pulse discharge current Iimp(10/350) µs1 kA
Total discharge current Itotal(8/20) µs10 kA
Total discharge current Itotal(10/350) µs2.5 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA (in total)
Nominal pulse current Ian (10/1000) µs (line-earth)200 A
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 800 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 800 V
Residual voltage at In(line-earth)≤ 70 V
Residual voltage with Ian (10/1000) µs (line-earth)≤ 28 V
Voltage protection level Up(line-earth)≤ 900 V (C2 - 10 kV/5 kA, spike)
≤ 70 V (C2 - 10 kV/5 kA, static)
≤ 1 kV (C3 - 7.5 kV / 100 A, spike)
≤ 30 V (C3 - 7.5 kV / 100 A, static)
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.
Input attenuation aE, asym.0.5 dB (≤ 10 MHz)
0.6 dB (up to 60 MHz in 100 Ω system)
1 dB (up to 100 MHz, 100 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system> 100 MHz
Capacity (line-earth)5 pF (f=1 MHz / VR= 0 V)
Resistance in series5.5 Ω ±1.5 Ω (symmetry: +/- 0.5 Ω)
Surge protection fault messagenone
Impulse durability (line-earth)C2 - 4 kV/2 kA
C3 - 100 A
B2 - 4 kV/100 A
D1 - 1 kA
Alternating current carrying capacity (line-earth)5 A - 1 s

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection method INCOMTRAB plug-in system
Connection method OUTCOMTRAB plug-in system
Connection technologyLSA-PLUS

Connection, equipotential bonding

Connection methodSpring contact

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2002

Classifications


ETIM for 2838623 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 180 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.