View larger
FLT-ISG-100-EX
2905579
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2905579 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 78 (C-4-2017) |
| GTIN | 4055626002446 |
| Weight per Piece (excluding packing) | 285.400 g |
| Custom tariff number | 73269098 |
| Country of origin | DE (Germany) |
| Degree of protection | IP67 (according to IEC 60529) |
|---|---|
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 60 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 95 % (According to DIN ISO 60068-2-30 method 1) |
| Mounting type | Screw mounting |
|---|---|
| Color | traffic grey A RAL 7042 |
| Type | Screw-on module |
| Surge protection fault message | none |
| Note | Connection: screw (DIN 933), M10x25, wrench size: 17 mm, spring washer (DIN 7980), size: 10 |
|---|
| Nominal discharge current In(8/20) µs | 100 kA |
|---|---|
| Maximum discharge current Imax(8/20) µs (Shield-Earth) | 100 kA |
| Alternating voltage response Uaw | ≤ 0.5 kV |
| Rated power-frequency withstand voltage UwAC | 250 V AC |
| Rated DC withstand voltage UwDC | 354 V DC |
| Rated impulse sparkover voltage Ur imp | ≤ 1.25 kV |
| Rated alternating discharge current | 500 A / 0.2 s (at 50/60 Hz, max. discharge current in the event of external voltage influence at the installation location) |
| Response time tA | ≤ 100 ns |
| ATEX | II 2 G Ex d IIC T6 Gb |
|---|---|
| II 2 D Ex tb IIIC T80 °C Db IP 66/67 | |
| IECEx | Ex d IIC T6 Gb |
| Ex tb IIIC T80 °C Db IP66/67 |
| Feature Name | Feature Value |
|---|---|
| Voltage (EF002355) | 250 kV |