PHOENIX CONTACT VAL-SEC-T2-3S-350VF-FM VAL-SEC-T2-3S-350VF-FM 2909590 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-3S-350VF-FM 2909590 PHOENIX CONTACT Type 2 surge arrester

VAL-SEC-T2-3S-350VF-FM

2909590

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Plug-in surge protection device with leakage current proof, according to type 2/class II, for three-phase power supply networks with N and PE separated (5-conductor system: L1, L2, L3, N, PE), with remote indication contact.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Pluggable surge protective device free of leakage current, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorlight grey RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions4
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)350 V AC
Maximum continuous operating voltage UC(L-PE)350 V AC
Maximum continuous voltage UC(N-PE)264 V AC
Rated load current IL40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (L-N)10 kA
Nominal discharge current In(8/20) µs (L-PE)10 kA
Nominal discharge current In(8/20) µs (N-PE)20 kA
Maximum discharge current Imax(8/20) µs (L-N)20 kA
Maximum discharge current Imax(8/20) µs (L-PE)20 kA
Maximum discharge current Imax(8/20) µs (N-PE)40 kA
Follow current interrupt rating Ifi(N-PE)100 A (264 V AC)
Short-circuit current rating ISCCR50 kA
Voltage protection level Up(L-N)≤ 1.5 kV
Voltage protection level Up(L-PE)≤ 2.3 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
Residual voltage Ures(L-N)≤ 1.35 kV (at In)
≤ 1.1 kV (at 5 kA)
≤ 0.95 kV (at 2 kA)
≤ 0.9 kV (At 1 kA)
Residual voltage Ures(L-PE)≤ 1.75 kV (at In)
≤ 1.2 kV (at 5 kA)
≤ 1.05 kV (at 2 kA)
≤ 0.95 kV (At 1 kA)
Residual voltage Ures(N-PE)≤ 0.5 kV (at In)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.5 kV (at 4 kA)
≤ 0.5 kV (at 2 kA)
TOV behavior at UT(L-N)457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with V-type through wiring40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring200 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 6 mm²

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

eCl@ss

eCl@ss 5.127130801
eCl@ss 6.027130805
eCl@ss 8.027130805
eCl@ss 9.027130805

ETIM

ETIM 5.0EC000941
ETIM 6.0EC000941

UNSPSC

UNSPSC 13.239121620

ETIM for 2909590 Earthing, lightning and surge protection (EC000941)
Feature Name Feature Value
System configuration DC (EF009926) No
System configuration IT (EF009927) No
System configuration TN (EF009928) No
System configuration TN-C (EF009929) No
System configuration TN-C-S (EF009933) No
System configuration TN-S (EF009930) Yes
System configuration TT (EF009931) No
System configuration other (EF009932) No
Nominal discharge surge current (8/20) (EF004214) 10 kA
Max. discharge surge current (8/20) (EF012274) 20 kA
Max. continuous voltage AC (EF004198) 350 V
Voltage protection level (EF003525) 2.3 kV
Voltage protection level L-N (EF004236) 1.5 kV
Voltage protection level N-PE (EF008796) 1.5 kV
Max. overcurrent protection device, parallel connection (fuse) (EF015962) 200 A
Max. overcurrent protection device, series connection (fuse) (EF015963) 40 A
Short-circuit breaking capacity (Isccr) (EF012627) 50 kA
Integrated backup fuse (EF008797) Yes
Leakage-current free (EF016002) No
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) Other
Max. conductor cross section solid (solid, stranded) (EF008827) 2.5 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 16 mm²
With remote signalling contact (EF000422) Yes
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) Yes
Degree of protection (IP) (EF005474) IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.