Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Product type | Interface module |
| Product family | VIP I/O-Marshalling |
| Set comprises | 1433798 IOA FEED-THRU/EX/BULK PACK |
| No. of channels | 1 |
| Operating mode | 100% operating factor |
| Data management status | |
| Article revision | 05 |
| Insulation characteristics | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Max. operating voltage Umax | 30 V |
| Max. permissible current | 1 A |
| Nominal voltage UN | 24 V DC |
| Max. current carrying capacity per branch | 1 A |
| Nominal supply voltage | 24 V DC |
| Continuous load current | 1 A |
| Control circuits | |
| Connection method | Pin strip |
| Number of connections | 1 |
| Number of positions | 13 |
| Safety data | |
| Input voltage Ui | 30 V |
| Input current Ii | 1 A |
| Inductance Li | 0 mH |
| Capacitance Ci | 0 µF |
| Max. output voltage Uo | Ui |
| Max. output current Io | Ii |
| Max. output power Po | Pi |
| Status display | no |
| Status display present | No |
| Item dimensions | |
| Width | 10.3 mm |
| Height | 64.2 mm |
| Depth | 72.9 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 75 °C |
| Ambient temperature (storage/transport) | -40 °C ... 75 °C |
| Altitude | < 2000 m |
| Permissible humidity (operation) | 0 % ... 95 % (non-condensing) |
| ATEX | |
| Identification | II 3G Ex nA IIC T4 Gc |
| Certificate | CSANe 21ATEX4128X |
| IECEx | |
| Identification | Ex nA IIC T4 Gc |
| Certificate | IECEx CSAE 21.0004X |
| UKEX | |
| Identification | II 3G Ex nA IIC T4 Gc |
| Certificate | PxCIF23UKEX2906598X |
| UL, USA/Canada | |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
| Class I, Zone 2, IIC T4 | |
| CSA, USA/Canada | |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
| Class I, Zone 2, AEx nA IIC T4 Gc | |
| Ex nA IIC T4 Gc | |
| Standards/regulations | IEC 60664 |
| DIN EN 50178 |
| Mounting position | any |