View larger
IB IL UTH 4/J-ECO
2702502
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2702502 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 143 (C-6-2017) |
| GTIN | 4055626206059 |
| Weight per Piece (excluding packing) | 69.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
| Ambient temperature (operation) | 0 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
| Mounting type | DIN rail |
|---|---|
| Net weight | 69 g |
| Note on weight specifications | with connector |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Checksum error I/O error message sent to the bus coupler |
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 38 mA |
| max. 55 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 32 mA |
| max. 39 mA | |
| Power consumption | typ. 1.05 W (total) |
| Number of inputs | 4 (type J) |
|---|---|
| Input name | Analog UTH inputs |
| Description of the input | Differential inputs |
| Connection method | Inline connector |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded |
| Sensor types that can be used (TC) | J |
| Measuring principle | Sigma/Delta process |
| Measured value representation | 16 bits (15 bits + sign bit) |
| A/D conversion time | typ. 120 ms |
| Resolution A/D | 24 bit |
| Process data update | < 10 ms |
| Type of protection | Transient protection of inputs |
| Test section | Bus logic (local bus, communications power) 500 V AC 50 Hz 1 min. |
|---|---|
| Analog I/O 500 V AC 50 Hz 1 min. | |
| Functional earth ground 500 V AC 50 Hz 1 min. |
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |