PHOENIX CONTACT ELR H3-IES-PT-24DC/500AC-2 ELR H3-IES-PT- 24DC/500AC-2 2903916 PHOENIX CONTACT Hybrid motor starter View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ELR H3-IES-PT- 24DC/500AC-2 2903916 PHOENIX CONTACT Hybrid motor starter

ELR H3-IES-PT-24DC/500AC-2

2903916

PHOENIX CONTACT

1 Pcs.

Hybrid motor starter Hybrid start controller for starting 3~ AC motors up to 500 V AC and 2.4 A output current, with 24 V DC control voltage, adjustable overload disconnect, emergency stop function up to SIL 3/PL e and push-in connection. Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 2.4 A output current, with 24 V DC control voltage, adjustable overload shutdown, emergency stop function to SIL 3/PL e, and push-in connection.

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
Notes on operationIf this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board.

Product properties
Product typeHybrid motor starters
Product familyCONTACTRON
Operating mode100% operating factor
Data management status
Article revision05

Electrical properties
Number of phases3
Motor starter typeDirect starter
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation for nominal condition2.2 W
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation3.3 W
Minimum power dissipation1.1 W
Coordination type1
Supply
Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS40 mA
Protective circuitSurge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage500 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC

Input data
Control
Input nameControl input
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC5 mA (Input type 1)
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms
Protective circuitReverse polarity protection

Output data
AC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie2.4 A (AC-51)
2.4 A (AC-53a)
Mains frequency50/60 Hz
Load current range180 mA ... 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Cooling time20 min. (for auto reset)
Leakage current0 mA
Protective circuitSurge protection
Acknowledge output
NoteConfirmation: floating change-over contact, signal contact
Contact switching type1 changeover contact
Switching capacity in accordance with IEC 60947-5-13 A (230 V, AC15)
2 A (24 V, DC13)

Connection data
Control circuits
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Load circuit
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Signaling
Status displayLED (yellow)
Operating voltage displayGreen LED
Error indicationRed LED

Dimensions
Width22.5 mm
Height107.5 mm
Depth114 mm

Material specifications
Flammability rating according to UL 94V0 (Housing)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m

Approvals
UKCA
CertificateUKCA-compliant
ATEX
Identification II (2) G [Ex e] [Ex d] [Ex px]
 II (2) D [Ex t] [Ex p]
CertificatePTB 07 ATEX 3145
UL approval
CertificateNLDX.E228652
Safety Integrity Level (SIL, IEC 61508)
Identification≤ 3
NoteSafe shutdown
Safety Integrity Level (SIL, IEC 61508)
Identification2
NoteMotor protection
Performance Level (ISO 13849)
Identification≤ e
NoteSafe shutdown
Category (ISO 13849)
Identification≤ 3
NoteSafe shutdown
UL data
SCCR100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA2.4 A (500 V AC)
Group installation20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category codeNLDX

Standards and regulations
Standards/regulations
Standards/regulationsIEC 60947-1
IEC 60947-4-2
IEC 61508
ISO 13849

Mounting
Mounting typeDIN rail mounting
Assembly notealignable, for spacing see derating
Mounting positionvertical (horizontal DIN rail, motor output below)

ETIM for 2903916 Low-voltage industrial controls and switchgear (EC001037)
Feature Name Feature Value
Type of motor starter (EF009598) Direct starter
With short-circuit release (EF006691) No
Rated control supply voltage DC (EF003980) 19.2 V
Rated operation current Ie (EF001443) 2.4 A
Rated operation current at AC-3, 400 V (EF009602) 2.4 A
Overload release current setting (EF002336) 0.18 A
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Temperature compensated overload protection (EF009604) No
Release class (EF006668) CLASS 10
Type of electrical connection of main circuit (EF006819) Spring clamp connection
Type of electrical connection for auxiliary- and control current circuit (EF006979) Spring clamp connection
Suitable for rail mounting (EF003972) Yes
Number of command positions (EF001372) 1
Suitable for emergency stop (EF001433) Yes
External reset possible (EF003426) Yes
Degree of protection (IP) (EF005474) IP20
Width (EF000008) 22.5 mm
Height (EF000040) 107.5 mm
Depth (EF000049) 114 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.