PHOENIX CONTACT HCC 4-CLT-NS35 SET HCC 4-CLT-NS35 SET 1279180 PHOENIX CONTACT Surge Protection Base Element, For CLIXTRAB Surge Protection, Sui.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

HCC 4-CLT-NS35 SET 1279180 PHOENIX CONTACT Surge Protection Base Element, For CLIXTRAB Surge Protection, Sui..

HCC 4-CLT-NS35 SET

1279180

PHOENIX CONTACT

50 Pcs.

Surge Protection Base Element, For CLIXTRAB Surge Protection, Suitable for HCC 4 Series, Nominal Voltage: 400 V, Mounting Class: NS 35/7.5, NS 35/15, Color: Grey CLIXTRAB surge protection base element, for surge protection suitable for the HCC 4 series, rated voltage: 400 V, mounting type: NS 35/7.5, NS 35/15, colour: grey

Automation > Installation clamp for meters
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Notes
General notesfor surge protection CLIXTRAB suitable for the HCC 4 series
General notes
noteThe use of surge protection plugs reduces the load current of the terminal block (see technical data for CLT surge protection plugs).

Article features
Product TypeFeed-through clamp
No. of poles10
Number of connections10
Insulation characteristics
Overvoltage CategoryIii
Degree of pollution2

Electrical characteristics
Sizing Impulse Voltage4 kV

Connection data
Number of connections per plan10
Standard-compliant connectionIEC 61984
Nominal voltage400 V

dimensions
width72.6 mm
height75.9 mm
Depth35.3 mm

Material information
Colorgrey
Combustibility class according to UL 94V0
Insulation Material GroupThe
Insulation materialPA
Cold static insulation material insert-60 °C
Insulation Material Relative Temperature Index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Surface Flammability NFPA 130 (ASTM E 162)Exceeded
NFPA 130 (ASTM E 662) Specific Optical Density of FumesExceeded
NFPA 130 Fume Toxicity (SMP 800C)Exceeded

Environmental and electrical life conditions
Broadband vibration/noise
Test SpecificationDIN EN 50155 (VDE 0115-200):2018-05
SpectrumElectrical Life Check Category 1, Class B, Body Mounted
Frequencyf1= 5 Hz a f2= 150 Hz
ASD Level0.964 (m/s²)²/Hz
Acceleration0.58g
Test duration per axle5 h
Test DirectionsX, Y, and Z axis
ResultTest passed
Shock
Test SpecificationDIN EN 50155 (VDE 0115-200):2018-05
Shock FormSemi-sinusoidal
Acceleration5g
Shock Duration30 ms
Number of shocks per direction3
Test DirectionsX, Y and Z axis (pos. and neg.)
ResultTest passed
Environmental conditions
Ambient temperature (operating)-60 °C (for maximum operating temperature see derating curve)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for short duration, no longer than 24 h, -60 °C °C to +70 °C)
Ambient temperature (mounting)-5 °C ... 70 °C
Ambient Temperature (Activation)-5 °C ... 70 °C
Permissible humidity (storage/transport)30 % ... 70 %

Regulations and requirements
Standard-compliant connectionIEC 61984

Montage
Mounting typeNS 35/7.5
NS 35/15

Product Datasheet